BLD07-01578
| FIRE-Final Inspection | 7/24/2008 | 7/24/2008 | 7/24/2008 5:11:48 PM | P | PASS |
|
|
Fire life safety finaled.
|
FIR08-00355
| INSP-Final Inspection | 7/24/2008 | 7/24/2008 | 7/24/2008 5:11:23 PM | P | PASS |
|
|
Fire alarm permit finaled.
|
FIR08-00182
| INSP-Sprinkler Rough-in/Hydro | 7/24/2008 | 7/24/2008 | 7/24/2008 5:09:15 PM | P | NR |
|
|
|
FIR07-01051
| INSP-Sprinkler Rough-in | 7/24/2008 | 7/24/2008 | 7/24/2008 3:19:18 PM | P | NR |
|
|
wip
|
FIR08-00319
| INSP-Sprinkler Rough-in | 7/23/2008 | 7/24/2008 | 7/24/2008 3:18:48 PM | A | PART |
|
|
Hard lid ceilings at the mens and womens restroom only are okay for cover pending approved plans match piping install, also okayed brace at the 4" main adjacent to the lion's den. Discussed UG flusing and hydro testing schedule.
|
FIR07-00606
| INSP-Sprinkler Rough-in | 7/23/2008 | 7/24/2008 | 7/24/2008 3:15:55 PM | A | FAIL |
|
|
OH re-inspection for area A failed due to several deficient items including overspaced upright coverage at the auditorium, SW heads at an electrical room are too low, foil at heads in the stage area, piping changes for branch line feeds in the hyd. calc area at the prop storage room, missing flex couplings at two locations, lacking coverage at the administration vestibule, missing EQ brace at the admin. main, new plans need to reflect the added uprights and piping changes for mains and branchlines. Some issues previously noted are corrected including seismic bracing at the auditorium and added coverage for the stair landing and main entry vestibule.
|
FIR08-00262
| FIR-Aging Inspection | 7/24/2008 | 7/24/2008 | 7/24/2008 12:39:23 PM | | DEFR |
|
|
Pending completion of work for field inspection.
|
BLD08-01265
| FIRE-Conference | 7/24/2008 | 7/24/2008 | 7/24/2008 12:34:58 PM | A | DONE |
|
|
On site conference regarding approved door hardware at several locations.
|
BLD08-01018
| FIRE-Final Inspection | 7/23/2008 | 7/24/2008 | 7/24/2008 12:33:59 PM | A | PASS |
|
|
Verified correction notice items are complete, two exit signs repaired by contractor while on site, life safety inspection passed.
|