FIR09-00242
| FIR-Aging Inspection | 7/24/2009 | 7/24/2009 | 7/27/2009 9:06:51 AM | | DEFR |
|
|
|
FIR09-00394
| INSP-Sprinkler Rough-in/Hydro | 7/23/2009 | 7/24/2009 | 7/24/2009 3:29:13 PM | P | PART |
|
|
See stamped plan set on site for locations inspected today and approved for cover at the sheetrock ceilings including the 1st floor lobby.
|
FIR09-00033
| INSP-Sprinkler Rough-in/Hydro | 7/24/2009 | 7/24/2009 | 7/24/2009 3:26:55 PM | P | PART |
|
|
Trip testing completed acceptable for rack systems # 26 and 27 at the freezer area.
|
FIR09-00317
| INSP-Sprinkler Rough-in | 7/23/2009 | 7/24/2009 | 7/24/2009 3:25:35 PM | A | PART |
|
|
Underground fire supply line approved for cover, need to install cap or blind flange at the riser stub.
|
BLD09-00797
| FIRE-Final Inspection | 7/23/2009 | 7/24/2009 | 7/24/2009 3:24:23 PM | A | PASS |
|
|
Items listed on the previous correction notice are finished, fire life safety is satisfactory.
|
FIR09-00033
| INSP-Sprinkler Rough-in/Hydro | 7/21/2009 | 7/24/2009 | 7/24/2009 3:23:10 PM | A | PART |
|
|
Hydrostatic re-test for systems #1, 2 and 5 passed.
|
FIR08-00445
| INSP-Final Inspection | 7/21/2009 | 7/24/2009 | 7/24/2009 1:15:25 PM | A | NR |
|
|
Project is not in condition for final, missing fixtures for verification of proper coverage, escutcheons not installed, finishes incomplete, etc.
|
FIR08-00442
| INSP-Final Inspection | 7/21/2009 | 7/24/2009 | 7/24/2009 1:10:30 PM | A | PASS |
|
|
Fire sprinkler permit final walkthrough passed.
|
FIR08-00437
| INSP-Sprinkler Rough-in/Hydro | 7/21/2009 | 7/24/2009 | 7/24/2009 1:04:45 PM | A | PASS |
|
|
Fire sprinkler permit work finaled.
|
FIR08-00440
| INSP-Final Inspection | 7/21/2009 | 7/24/2009 | 7/24/2009 1:04:14 PM | A | FAIL |
|
|
Missing escutcheons, some heads are covered with tape/paper, tenant area not completed for final at this time.
|
FIR08-00444
| INSP-Final Inspection | 7/21/2009 | 7/24/2009 | 7/24/2009 1:02:56 PM | A | FAIL |
|
|
Pendent head coverage at the master closet is obstructed by an adjacent surface mounted light fixture.
|
BLD08-01138
| FIRE-Final Inspection | 7/23/2009 | 7/24/2009 | 7/24/2009 12:57:09 PM | A | PASS |
|
|
Fire life safety passed inspection, noted the fire extinguishers in the common corridor are two months overdue annual certification per the dated inspection tag.
|
BLD08-01139
| FIRE-Final Inspection | 7/23/2009 | 7/24/2009 | 7/24/2009 12:55:27 PM | A | PASS |
|
|
Fire life safety approved for final.
|
FIR09-00201
| INSP-Final Inspection | 7/23/2009 | 7/24/2009 | 7/24/2009 12:54:57 PM | A | PASS |
|
|
Fire alarm work passed final inspection.
|
FIR09-00200
| INSP-Final Inspection | 7/23/2009 | 7/24/2009 | 7/24/2009 12:54:23 PM | A | PASS |
|
|
Fire alarm work passed field inspection, permit finaled.
|
FIR08-00581
| INSP-Sprinkler Rough-in | 7/21/2009 | 7/24/2009 | 7/24/2009 12:53:41 PM | A | PART |
|
|
Overhead install is approved for cover at the hard lid areas.
|
FIR08-00580
| INSP-Sprinkler Rough-in | 7/21/2009 | 7/24/2009 | 7/24/2009 12:53:05 PM | A | PART |
|
|
Overhead rough-in okayed for cover at the sheetrock ceilings.
|
FIR08-00571
| INSP-Sprinkler Rough-in | 7/21/2009 | 7/24/2009 | 7/24/2009 12:51:57 PM | A | NR |
|
|
Work currently underway, installation is not yet completed for inspection as requested.
|
FIR09-00316
| INSP-Final Inspection | 7/23/2009 | 7/24/2009 | 7/24/2009 12:50:22 PM | A | DEFR |
|
|
Randy or Kelly ###-#### Phone #: ###-####
|