Inspections for the day of: Friday, July 24, 2009.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00242 FIR-Aging Inspection7/24/20097/24/20097/27/2009 9:06:51 AM DEFR
FIR09-00394 INSP-Sprinkler Rough-in/Hydro7/23/20097/24/20097/24/2009 3:29:13 PMPPART
See stamped plan set on site for locations inspected today and approved for cover at the sheetrock ceilings including the 1st floor lobby.
FIR09-00033 INSP-Sprinkler Rough-in/Hydro7/24/20097/24/20097/24/2009 3:26:55 PMPPART
Trip testing completed acceptable for rack systems # 26 and 27 at the freezer area.
FIR09-00317 INSP-Sprinkler Rough-in7/23/20097/24/20097/24/2009 3:25:35 PMAPART
Underground fire supply line approved for cover, need to install cap or blind flange at the riser stub.
BLD09-00797 FIRE-Final Inspection7/23/20097/24/20097/24/2009 3:24:23 PMAPASS
Items listed on the previous correction notice are finished, fire life safety is satisfactory.
FIR09-00033 INSP-Sprinkler Rough-in/Hydro7/21/20097/24/20097/24/2009 3:23:10 PMAPART
Hydrostatic re-test for systems #1, 2 and 5 passed.
FIR08-00445 INSP-Final Inspection7/21/20097/24/20097/24/2009 1:15:25 PMANR
Project is not in condition for final, missing fixtures for verification of proper coverage, escutcheons not installed, finishes incomplete, etc.
FIR08-00442 INSP-Final Inspection7/21/20097/24/20097/24/2009 1:10:30 PMAPASS
Fire sprinkler permit final walkthrough passed.
FIR08-00437 INSP-Sprinkler Rough-in/Hydro7/21/20097/24/20097/24/2009 1:04:45 PMAPASS
Fire sprinkler permit work finaled.
FIR08-00440 INSP-Final Inspection7/21/20097/24/20097/24/2009 1:04:14 PMAFAIL
Missing escutcheons, some heads are covered with tape/paper, tenant area not completed for final at this time.
FIR08-00444 INSP-Final Inspection7/21/20097/24/20097/24/2009 1:02:56 PMAFAIL
Pendent head coverage at the master closet is obstructed by an adjacent surface mounted light fixture.
BLD08-01138 FIRE-Final Inspection7/23/20097/24/20097/24/2009 12:57:09 PMAPASS
Fire life safety passed inspection, noted the fire extinguishers in the common corridor are two months overdue annual certification per the dated inspection tag.
BLD08-01139 FIRE-Final Inspection7/23/20097/24/20097/24/2009 12:55:27 PMAPASS
Fire life safety approved for final.
FIR09-00201 INSP-Final Inspection7/23/20097/24/20097/24/2009 12:54:57 PMAPASS
Fire alarm work passed final inspection.
FIR09-00200 INSP-Final Inspection7/23/20097/24/20097/24/2009 12:54:23 PMAPASS
Fire alarm work passed field inspection, permit finaled.
FIR08-00581 INSP-Sprinkler Rough-in7/21/20097/24/20097/24/2009 12:53:41 PMAPART
Overhead install is approved for cover at the hard lid areas.
FIR08-00580 INSP-Sprinkler Rough-in7/21/20097/24/20097/24/2009 12:53:05 PMAPART
Overhead rough-in okayed for cover at the sheetrock ceilings.
FIR08-00571 INSP-Sprinkler Rough-in7/21/20097/24/20097/24/2009 12:51:57 PMANR
Work currently underway, installation is not yet completed for inspection as requested.
FIR09-00316 INSP-Final Inspection7/23/20097/24/20097/24/2009 12:50:22 PMADEFR