FIR14-00628
| INSP-Final Inspection | 7/23/2015 | 7/24/2015 | 7/24/2015 3:16:06 PM | A | PART |
|
|
Trip test of the dry pipe valve, including the new accelerator - tested OK within 45 seconds. Escutcheons missing on multiple heads in parking area, need to have air maintenance installed on air line supply to dry system, compressor provided regulator not approved for air maintenance.
|
BLD14-01936
| FIRE-Final Inspection | 7/23/2015 | 7/24/2015 | 7/24/2015 2:39:14 PM | A | PASS |
|
|
Temporary occupancy approved for life fire safety, verbally confirmed with electrical contractor that the fire alarm system has capability to sustain visual notification for rooms occupied by hearing impaired tenants. Electrical contractor needs to provide information on heat tape used on fire sprinkler system before final sign off can occur.
*Above item confirmed - 325*
|
BLD14-02406
| FIRE-Final Inspection | 7/23/2015 | 7/24/2015 | 7/24/2015 2:38:24 PM | A | PASS |
|
|
Temporary occupancy approved for life fire safety, verbally confirmed with electrical contractor that the fire alarm system has capability to sustain visual notification for rooms occupied by hearing impaired tenants. Electrical contractor needs to provide information on heat tape used on fire sprinkler system before final sign off can occur.
*Above item confirmed* - 325
|
BLD14-01938
| FIRE-Final Inspection | 7/23/2015 | 7/24/2015 | 7/24/2015 2:37:31 PM | A | PASS |
|
|
Temporary occupancy approved for life fire safety, verbally confirmed with electrical contractor that the fire alarm system has capability to sustain visual notification for rooms occupied by hearing impaired tenants. Electrical contractor needs to provide information on heat tape used on fire sprinkler system before final sign off can occur.
*Above item confirmed - 325*
|
BLD14-01937
| FIRE-Final Inspection | 7/23/2015 | 7/24/2015 | 7/24/2015 2:36:43 PM | A | PASS |
|
|
*****10-27-15 as per Scott A. all fire life inspections have passed and ready for perm c of o****Temporary occupancy approved for life fire safety, verbally confirmed with electrical contractor that the fire alarm system has capability to sustain visual notification for rooms occupied by hearing impaired tenants. Electrical contractor needs to provide information on heat tape used on fire sprinkler system before final sign off can occur.
|
FIR14-00850
| INSP-Final Inspection | 7/24/2015 | 7/24/2015 | 7/24/2015 2:31:07 PM | A | PASS |
|
|
Alarm inspection complete,verbally confirmed with electrical contractor that the fire alarm system has capability to sustain visual notification for rooms designated for hearing impaired tenants. Heat tape for wet system main is now monitored at FACP. Electrical contractor needs to provide information on heat tape used before final sign off can occur.
|
FIR15-00089
| INSP-Final Inspection | 7/24/2015 | 7/24/2015 | 7/24/2015 2:17:10 PM | P | PASS |
|
|
Fire sprinkler inspection passed/complete
|
BLD15-01589
| FIRE-Final Inspection | 7/23/2015 | 7/24/2015 | 7/24/2015 9:00:58 AM | A | PASS |
|
|
Life fire safety passed/complete
|
FIR15-00096
| INSP-Sprinkler Rough-in | 7/23/2015 | 7/24/2015 | 7/24/2015 8:48:32 AM | A | PART |
|
|
Inspected drop down ceiling area's in rooms 502, 525, 529, approved for cover. Verified with contractor list for the 5th floor apartment rooms, all rooms inspected for rough to cover.
|
BLD15-01729
| FIRE-Conference | 7/24/2015 | 7/24/2015 | 7/24/2015 8:27:11 AM | P | DONE |
|
|
Zach Phone #: ###-####, informed me that the tenant that will be occupying this space is being "Kicked Out" of their current tenant space at the end of next week. He is requesting that we approve them to occupy half of the space after August 1st, providing that the half they occupy is inspected and those area’s pass inspection. I instructed Zach that I will talk to Scott Arellano about the issue, and that I did not have the authority to give an approval. Zach instructed to me that he will be calling in inspections next week for the area's they are requesting to occupy.
|
FIR15-00469
| INSP-Conference | 7/23/2015 | 7/24/2015 | 7/24/2015 8:01:36 AM | A | CANC |
|
|
Zack-GC, phone number ###-####, called in a conference for BLD15-01729, the tenant space , not the FIR permit.
|
FIR14-00807
| INSP-Supply line flush | 7/24/2015 | 7/24/2015 | 7/24/2015 12:00:00 AM | P | CANC |
|
|
Jermy Phone #: ###-####
|