Inspections for the day of: Monday, July 24, 2017.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-01656 Final7/24/20177/24/20177/24/2017 2:32:41 PMPFAIL
Shane is the contact his cell no ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates
400.17- Where cable travels over parking garage wall down 25' strain relief shall be in place to prevent tension on terminals in disconnect.
ELE16-03931 Electrical Rough-In7/24/20177/24/20177/24/2017 2:05:03 PMPPASS
utility 734, shaft wall units 305-705 Phone #: ###-#### Inspection requested via web by Cathy Duchek
305 thru 705 duct shaft and utility 734 walls. Areas noted on inspection print rough in ok cover
ELE16-00580 Electrical Rough-In7/24/20177/24/20177/24/2017 2:03:32 PMPPASS
mci feeders in garage going in shaft wall Phone #: ###-#### Inspection requested via web by Cathy Duchek
Vertical shafts in garage for feeders rough in ok cover
ELE15-03035 Final7/21/20177/24/20177/24/2017 12:16:24 PMAPASS
Call paul with any questions at ###-####. RME has electrically tested and physically viewed the installation and accepts liability of the floor heat installation. thank you Phone #: ###-#### Inspection requested via web by Steve Blackmer
Final ok
ELE17-02096 Rough-In Permanent Service7/21/20177/24/20177/24/2017 9:58:00 AMAFAIL
Phone #: ###-#### Inspection requested via web by Rowdy Monroe
110.3-Allied pancake boxes not UL listed. Change to a listed product.
ELE17-02097 Rough-In Permanent Service7/21/20177/24/20177/24/2017 9:57:20 AMAFAIL
Phone #: ###-#### Inspection requested via web by Rowdy Monroe
110.3- Allied pancake boxes not UL listed. Change to a UL listed product.
ELE17-02297 Rough-In Permanent Service7/21/20177/24/20177/24/2017 9:17:22 AMAFAIL
Any issues plz let me know, thx, TW Phone #: ###-#### Inspection requested via web by Stephen Kren
Seperate BLD for pool exists no ELE yet.
210.52(A)(2)- Area above counter or work space count as wall space. Right of fireplace above flat is wall space needs receptacle outlet.
250.64(D)(1)- Grounding electrode tap shall be outside panel and extend to each disconnecting means.
300.4- Nail plates needed on pool HR upper plate and below 2 gang in nook.