Inspections for the day of: Tuesday, July 24, 2018.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBrian Scoles
TitleMEC INSPECTOR
Phone #914-4915
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC18-03331 Final7/24/20187/24/20187/24/2018 4:21:19 PMPPASS
after 4 pm- 2087899299- a/c coil co ok
MEC18-03615 Rough-in7/24/20187/24/20187/24/2018 3:41:26 PMPNR
Aaron Phone #: ###-####-please call 30 mintues prior to meet- should have \been conference- went over dryer ducting which is ok- went over range ducting and gas piping needs a pressure test 20psi on max 30lb gauge- will call in inspection when ready
MEC18-03578 Final7/23/20187/24/20187/24/2018 3:06:41 PMPFAIL
###-####- need secondary drain ran to outside or wet switch installed-
MEC18-03097 Pressure Test7/23/20187/24/20187/24/2018 2:49:34 PMPPASS
BRAD IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER- 60lb gas pass from new meter location to existing pipe
MEC18-03525 Final7/19/20187/24/20187/24/2018 2:30:12 PMPPASS
Please call Kyle to ensure install is complete. Thank you! ###-#### Phone #: ###-#### Inspection requested via web by Rick Borg- furnace a/c coil co ok
MEC18-03077 Final7/17/20187/24/20187/24/2018 2:02:06 PMPPASS
###-####- furnace a/c coil co ok
MEC17-04595 Final7/18/20187/24/20187/24/2018 1:41:18 PMPPASS
Please call Leana at ###-#### when on the way
Phone #: ###-#### Inspection requested via web by Ashley Stegemann- fireplace final ok
MEC18-01595 Rough-in7/24/20187/24/20187/24/2018 1:08:54 PMPPASS
please call 1 hr in advance Phone #: ###-#### Inspection requested via web by Nicholas Paige- seal on ducts ok- insulation ok- ok for ceiling tile to be installed
MEC18-03611 Final7/24/20187/24/20187/24/2018 12:41:20 PMPPASS
Inspection requested via web by Margie Rowe
MEC18-02215 Conference7/23/20187/24/20187/24/2018 11:55:13 AMADONE
Conference needed at 11:00 am please call Karl with any questions at 208 401 5600 thank you. Phone #: ###-#### Inspection requested via web by Karl Hestekin- discussed mock up and gas piping and fire protection location on duct or ansl system-
MEC18-02296 Rough-in7/24/20187/24/20187/24/2018 10:39:50 AMPPART
Phone #: ###-#### Inspection requested via web by Nicholas Paige- still installing registers- ok for border tiles only- recall in when finished
MEC18-03238 Final7/23/20187/24/20187/24/2018 10:31:43 AMANR
still need 1" clearance on single wall pipe off unit heater- talked to Dave about this
MEC18-03610 Pressure Test7/24/20187/24/20187/24/2018 10:15:43 AMAFAIL
Phone #: ###-#### Inspection requested via web by Oleg Chervak- gauge below 20psi- need to resubmit manual lay out of house does not match manual J- dryer vent needs supported every 4 feet
MEC18-03577 Final7/23/20187/24/20187/24/2018 10:03:34 AMAPASS
Please call homeowner Carmen with appt time: ###-#### Phone #: ###-#### Inspection requested via web by Michael Stimpson- minisplit final ok
MEC18-03077 Final7/17/20187/24/20187/24/2018 8:22:46 AMANH
###-####
MEC18-03409 Conference7/23/20187/24/20187/24/2018 8:13:50 AMACANC
Blast witness please.
9:30 AM
Questions please call Randy ###-#### Phone #: ###-#### Inspection requested via web by Randy Hart- need to reschedule as i already have meeting at this time- please call 1 day in avance to schedule duct blast tests
MEC16-03405 Mec-Aging Inspection7/24/20187/24/20187/24/2018 8:12:27 AM CANC
wip
MEC18-03123 Final7/18/20187/24/20187/24/2018 8:12:02 AMAPASS
Please call Steve in route to inspection ###-#### Phone #: ###-#### Inspection requested via web by Justin Osterhout- a/c coil co ok
MEC18-03556 Final7/20/20187/24/20187/23/2018 7:25:47 AMACANC
Call ahead to Sam at ###-#### - customer goes to work at 4:30pm so please do inspection before. Phone #: ###-#### >> Inspection requested via web by Sabrina DeHority Inspection cancelled from web by: Sabrina DeHority