Inspections for the day of: Tuesday, July 24, 2018.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBen Livingston
TitleMEC-COM/RES INSPECTOR
Phone #576-1208
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC18-03549 Final7/23/20187/24/20187/24/2018 3:26:29 PMPPASS
INSTALLER: JAROD ###-####
LATE PM INSPECTION IF POSSIBLE PLEASE. THANK YOU! Phone #: ###-#### Inspection requested via web by Aaron Alandt
MEC17-05816 Final7/24/20187/24/20187/24/2018 3:10:20 PMPFAIL
Bj 2085730755 Inspection requested via web by william kerwin
still need blast test and balance report
MEC18-03604 Rough-in7/23/20187/24/20187/24/2018 2:06:19 PMPFAIL
Les Phone #: ###-####
new gas piping needs to be tested
MEC18-03563 Final7/24/20187/24/20187/24/2018 1:42:02 PMPFAIL
Please call Colter Kamo prior to inspection. ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette
electrical conection on wall has no cover,
furnace room needs gasket on door and self closing hinges, also needs combustion air from out side
MEC18-03576 Pressure Test7/23/20187/24/20187/24/2018 1:22:26 PMPFAIL
If you area able to come in early afternoon please let us know. Gas will be shut of to residence. Thank you. Phone #: ###-#### Inspection requested via web by Gary Duncan
20 lb test needs to be on a 30lb gauge not 100lb
MEC18-00476 Pressure Test7/24/20187/24/20187/24/2018 1:12:46 PMPNR
Please call on way: Gener ###-#### Phone #: ###-#### Inspection requested via web by Krista Boss
MEC18-02534 Pressure Test7/23/20187/24/20187/24/2018 11:31:29 AMAPASS
Please inspect late AM. Phone #: ###-#### Inspection requested via web by Mary LaFayette
20lb gas
MEC18-03609 Rough-in7/23/20187/24/20187/24/2018 11:21:41 AMAPASS
Phone #: ###-#### Inspection requested via web by Ashley Stegemann
MEC18-01790 Final7/23/20187/24/20187/24/2018 11:16:08 AMAPASS
Ac: 1905 Inspection requested via web by Gary Reeves
MEC18-01516 Rough-in7/23/20187/24/20187/24/2018 10:42:33 AMAPASS
Gate codes are 1092, 6445 Phone #: ###-#### Inspection requested via web by kelly Martin
MEC18-03004 Pressure Test7/23/20187/24/20187/24/2018 10:32:52 AMAFAIL
Please call Ed at ###-#### to coordinate. Phone #: ###-#### Inspection requested via web by Sabrina DeHority
need approved striker plates on gas flex both foor and cieling,
need propper protection where its attatched to stud wall at gauge
flue test at zero
MEC18-03004 Final7/23/20187/24/20187/24/2018 10:32:09 AMAFAIL
Please call Ed at ###-#### to coordinate. Phone #: ###-#### Inspection requested via web by Sabrina DeHority
need to leave a ladder to access furnace, furnace in attic need 24" wide path and 30"x30" platform at control side of furnace, all bedrooms need a return path
MEC18-03281 Rough-in7/23/20187/24/20187/24/2018 10:04:29 AMAPASS
Wes Phone #: ###-####
MEC13-05469 Mec-Aging Inspection7/24/20187/24/20187/24/2018 9:50:39 AM CANC
MEC17-03739 Mec-Aging Inspection7/24/20187/24/20187/24/2018 9:50:31 AM CANC
MEC18-03513 Rough-in7/23/20187/24/20187/24/2018 8:36:30 AMAPASS
CLINT ###-#### Phone #: ###-#### Inspection requested via web by Mike Almanza
MEC18-03255 Final7/17/20187/24/20187/23/2018 3:31:57 PMPPASS
installer Jarod ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt
MEC18-03549 Final7/20/20187/24/20187/23/2018 11:04:12 AMPCANC
INSTALLER BRANDAN ###-#### Phone #: ###-#### >> Inspection requested via web by Aaron Alandt Inspection cancelled from web by: Aaron Alandt