Inspections for the day of: Friday, July 24, 2020.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Story
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE20-02574 Temporary Service7/23/20207/24/20207/24/2020 1:43:49 PMPPASS
overhead temp power pole !Thank you stay safe! Phone #: ###-#### Inspection requested via web by Charles Davis
t/s o/h n ok
ELE20-01566 Electrical Rough-In7/23/20207/24/20207/24/2020 1:34:51 PMPPASS
Grid Ceiling inspection for cover. Inspection requested via web by Steve McCloy
Suspended ceiling ok to cover
ELE19-04516 Electrical Rough-In7/23/20207/24/20207/24/2020 1:20:51 PMPPASS
South end under ground for club house Phone #: ###-#### Inspection requested via web by Stephanie Huston
U/G in slab ok to cover
ELE20-00558 Final7/23/20207/24/20207/24/2020 10:27:43 AMAFAIL
Final inspection at Apollo Parking Lot
Contact Rod Tomlinson
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek
AFC calc posted is 20,818 and main breaker rated at 10,000
Must replace main with a 25,000 frame
ELE20-02576 Final7/23/20207/24/20207/24/2020 9:50:18 AMACANC
call Nate Steffler --boies parks and recreation ###-#### ---for access Phone #: ###-#### Inspection requested via web by ron spen cer
Called contact-no response or access
ELE20-00599 Permanent Service7/23/20207/24/20207/24/2020 9:36:27 AMAPASS
Phone #: ###-#### Inspection requested via web by Tom Jenkins
p/s u/g n ok 1 meter needed
Service for new warehouse ok
ELE20-00599 Rough-In Permanent Service7/23/20207/24/20207/24/2020 9:35:41 AMACANC
Phone #: ###-#### Inspection requested via web by Tom Jenkins
ELE20-02255 Electrical Rough-In7/23/20207/24/20207/24/2020 9:03:40 AMAPASS
Jay Walters is the onsite contact - ###-#### Phone #: ###-#### Inspection requested via web by BRS Permitting
Verified U/L listing of equipment and scope of work/Approved plans on-site