Inspections for the day of: Thursday, July 25, 2002.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR02-00213 INSP-Alarm Testing7/24/20027/25/20027/25/2002 12:00:00 AMAPASS
fire alarm finaled 7/25/2002 8:16:38 AM
BLD99-00444 FIRE-Final Inspection7/24/20027/25/20027/25/2002 12:00:00 AMAPASS
fire life/safety finaled. structural inspector to verify the thumbturn has been removed from the rear door 7/25/2002 10:38:42 AM
FIR02-00217 INSP-Supply line flush7/24/20027/25/20027/25/2002 12:00:00 AMAPASS
flush of underground OK 7/25/2002 9:08:41 AM
FIR02-00217 INSP-Sprinkler Rough-in/Hydro7/24/20027/25/20027/25/2002 12:00:00 AMAPASS
hydro test for the underground, fdc, riser header and the overhead system east area OK 7/25/2002 1:18:48 PM
FIR00-00653 INSP-Final Inspection7/24/20027/25/20027/25/2002 12:00:00 AMAFAIL
Provide 19.5 ah batteries for panel, provide verification power supply will support the batteries, provide calculations of 14 awg wire for the notification circuit, provide verification that the HVAC units meet requirements of UMC 608 for not having duct smoke detectors 7/25/2002 9:40:50 AM
FIR02-00278 INSP-Final Inspection7/24/20027/25/20027/25/2002 12:00:00 AMPCANC
cancelled by the contractor 7/25/2002 10:54:23 AM
BLD02-00687 FIRE-Final Inspection7/24/20027/25/20027/25/2002 12:00:00 AMPPASS
fire life/safety finaled 7/25/2002 4:23:55 PM
BLD02-00757 FIRE-Final Inspection7/24/20027/25/20027/25/2002 12:00:00 AMPPASS
fire life/safety finaled 7/25/2002 4:24:07 PM