Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD03-00335 FIRE-Final Inspection7/24/20037/25/20037/25/2003 12:00:00 AMAFAIL
martin; Phone #: ###-#### repair emergency lights and test, provide automatic shutdown for hvac unit #2 and test all duct smoke detectors (contractor did not have the smoke to test with), remove lock from server room door, test the main entry/exit door magnetic locks for operation which were being installed during inspection 7/25/2003 1:49:46 PM
FIR03-00323 INSP-Final Inspection7/24/20037/25/20037/25/2003 12:00:00 AMAFAIL
Provide 18ah batteries for the fire alarm panel, provide signage on the door. resend signals since all alarms came in as undefined at the central station 7/25/2003 10:03:07 AM
FIR03-00348 INSP-Final Inspection7/24/20037/25/20037/25/2003 12:00:00 AMAFAIL
Provide 18ah batteries for the fire alarm panel, provide signage on the door. resend signals since all alarms came in as undefined at the central station 7/25/2003 10:03:33 AM
FIR03-00389 INSP-Final Inspection7/24/20037/25/20037/25/2003 12:00:00 AMAFAIL
Relocate manual pull station 10' away from the hood per IFC. Provide all submittals for finaling of project (Contractor only had one set) 7/25/2003 10:51:38 AM
BLD03-01459 FIRE-Conference7/25/20037/25/20037/25/2003 12:00:00 AMADONE
I spoke with the male owner about life safety issues. In paticular was door hardware which was incorrect. I verified items with Jason Blais. The male owner became quite verbally excited about the city and their personell and policies. I told him to have a nice day and left the premise. Next inspection should be fun
FIR03-00197 INSP-Final Inspection7/25/20037/25/20037/25/2003 12:00:00 AMPPASS
fire sprinklers finaled
BLD03-00106 FIRE-Final Inspection7/25/20037/25/20037/25/2003 12:00:00 AMPPASS
fire alarm, fire sprinkler and fire life safety finaled
FIR03-00324 INSP-Conference7/25/20037/25/20037/25/2003 12:00:00 AMPDONE
spoke with the alarm technician about horn/strobe height placement, delay of pressure switch activation and inspectors test as installed by the fire sprinkler contractor 7/25/2003 3:54:25 PM
FIR03-00367 INSP-Conference7/24/20037/25/20037/25/2003 12:00:00 AMPPASS
Underground supply piping is ok to cover. I spoke with Jeff at Treasure Valley Fire and told him that an updated underground plan will need to be provided to Bill Alexander since installation does not match the prints 7/25/2003 4:02:15 PM
FIR03-00248 INSP-Alarm Testing7/24/20037/25/20037/25/2003 12:00:00 AMPPASS
fire alarm finaled 7/25/2003 3:31:57 PM