BLD03-00335
| FIRE-Final Inspection | 7/24/2003 | 7/25/2003 | 7/25/2003 12:00:00 AM | A | FAIL |
|
|
martin; Phone #: ###-#### repair emergency lights and test, provide automatic shutdown for hvac unit #2 and test all duct smoke detectors (contractor did not have the smoke to test with), remove lock from server room door, test the main entry/exit door magnetic locks for operation which were being installed during inspection 7/25/2003 1:49:46 PM
|
FIR03-00323
| INSP-Final Inspection | 7/24/2003 | 7/25/2003 | 7/25/2003 12:00:00 AM | A | FAIL |
|
|
Provide 18ah batteries for the fire alarm panel, provide signage on the door. resend signals since all alarms came in as undefined at the central station 7/25/2003 10:03:07 AM
|
FIR03-00348
| INSP-Final Inspection | 7/24/2003 | 7/25/2003 | 7/25/2003 12:00:00 AM | A | FAIL |
|
|
Provide 18ah batteries for the fire alarm panel, provide signage on the door. resend signals since all alarms came in as undefined at the central station 7/25/2003 10:03:33 AM
|
FIR03-00389
| INSP-Final Inspection | 7/24/2003 | 7/25/2003 | 7/25/2003 12:00:00 AM | A | FAIL |
|
|
Relocate manual pull station 10' away from the hood per IFC. Provide all submittals for finaling of project (Contractor only had one set) 7/25/2003 10:51:38 AM
|
BLD03-01459
| FIRE-Conference | 7/25/2003 | 7/25/2003 | 7/25/2003 12:00:00 AM | A | DONE |
|
|
I spoke with the male owner about life safety issues. In paticular was door hardware which was incorrect. I verified items with Jason Blais. The male owner became quite verbally excited about the city and their personell and policies. I told him to have a nice day and left the premise. Next inspection should be fun
|
FIR03-00197
| INSP-Final Inspection | 7/25/2003 | 7/25/2003 | 7/25/2003 12:00:00 AM | P | PASS |
|
|
fire sprinklers finaled
|
BLD03-00106
| FIRE-Final Inspection | 7/25/2003 | 7/25/2003 | 7/25/2003 12:00:00 AM | P | PASS |
|
|
fire alarm, fire sprinkler and fire life safety finaled
|
FIR03-00324
| INSP-Conference | 7/25/2003 | 7/25/2003 | 7/25/2003 12:00:00 AM | P | DONE |
|
|
spoke with the alarm technician about horn/strobe height placement, delay of pressure switch activation and inspectors test as installed by the fire sprinkler contractor 7/25/2003 3:54:25 PM
|
FIR03-00367
| INSP-Conference | 7/24/2003 | 7/25/2003 | 7/25/2003 12:00:00 AM | P | PASS |
|
|
Underground supply piping is ok to cover. I spoke with Jeff at Treasure Valley Fire and told him that an updated underground plan will need to be provided to Bill Alexander since installation does not match the prints 7/25/2003 4:02:15 PM
|
FIR03-00248
| INSP-Alarm Testing | 7/24/2003 | 7/25/2003 | 7/25/2003 12:00:00 AM | P | PASS |
|
|
fire alarm finaled 7/25/2003 3:31:57 PM
|