Inspections for the day of: Monday, July 25, 2005.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-01982 Final7/25/20057/25/20057/25/2005 4:44:01 PMPPASS
bill ###-#### Internet Inspection Request from: Bob Glenn called contr, ok to final
ELE05-02076 Final7/25/20057/25/20057/25/2005 4:43:16 PMPPASS
Scheduled by a contractor via Hello! on 7/25/2005 at 9:26:04 AM. ok to final
ELE05-02668 Temporary Service7/25/20057/25/20057/25/2005 3:03:52 PMPPASS
clyde; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ts u/g n ok
ELE05-02666 Temporary Service7/25/20057/25/20057/25/2005 2:54:15 PMPPASS
clyde; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ts u/g n ok
ELE05-02667 Temporary Service7/25/20057/25/20057/25/2005 2:45:29 PMPPASS
clyde; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie t/s u/g n ok
ELE05-02669 Temporary Service7/25/20057/25/20057/25/2005 2:39:49 PMPFAIL
clyde; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie called contr, left corr notice, 250.52(A) rod electrodes shall be not less than 8'-0" long, fee due.
ELE05-02660 Rough-In Permanent Service7/25/20057/25/20057/25/2005 2:07:12 PMPPASS
clyde ###-#### ric ok p/s u/g n ok
ELE05-02646 Rough-In Permanent Service7/22/20057/25/20057/25/2005 1:22:29 PMPPASS
rowdy ###-#### called cont, left survey, 312.5 gnd elect condr shall be protected against abrasion, 300.4(D) nm cable shall be 1 1/4" from edge of framing member ric ok, p/s u/g n ok
ELE05-02295 Temporary Service7/25/20057/25/20057/25/2005 12:50:35 PMPFAIL
###-#### - VERNA call contr, left corr notice, fee due, BCC job id sticker shall be posted, 250.24(A) service shall be grounded,left message, 312.5 gnd elect conductor shall be protected from abrasion
ELE05-02671 Permanent Service7/25/20057/25/20057/25/2005 12:29:11 PMPFAIL
###-#### - JOE called contr, left corr notice,250.53(D)(2) and 250.56 2 gnd rods shall be installed
ELE05-02585 Electrical Rough-In7/24/20057/25/20057/25/2005 10:02:00 AMAFAIL
Scheduled by a contractor via Hello! on 7/24/2005 at 11:52:34 PM. Contact: ###-####. BCC All make up shall be done,300.4 (A)(2) nail plates shall be used with notches, 300.4(D) nm cable shall be 1 1/4" from edge of framing member, 300.14 6" of free conductor shall be at each sw and recpt, 210.12(B) bedrooms branch ckts shall be protected by afci, 250.80 metal boxes shall be gnded, 314.19 boxes shall be closed, 314.20 boxes shall be mounted so front edge of box is not set back, nm shall be stapled within 8" of box and 4 1/2'. met owner, left corr notice
ELE05-02589 Electrical Rough-In7/22/20057/25/20057/25/2005 9:52:59 AMACANC
Phone #: ###-#### Internet Inspection Request from: Tyler Bowen see rip
ELE05-02645 Temporary Service7/22/20057/25/20057/25/2005 9:21:59 AMAPASS
rowdy ###-#### t/s u/g n ok
ELE05-02593 Temporary Service7/22/20057/25/20057/25/2005 8:26:23 AMAFAIL
North off McMillan between Cloverdale and Eagle, in Brookdale Meadows Sub.; Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot called contr, left corr notice, 312.5 gnd electrode conductor shall be protected from abrasion, 110.12(C) 120 v recpt shall not be broken and 20 a breaker shall clamp onto bus. Debris shall be removed from meter. Re-inspection fee due
ELE05-02631 Electrical Rough-In7/22/20057/25/20057/25/2005 8:09:23 AMAPASS
Building #3 East - Trench cover ; Phone #: ###-#### Internet Inspection Request from: Celinda Winters ok to cover u/g under slab
ELE05-02630 Electrical Rough-In7/22/20057/25/20057/25/2005 8:08:40 AMAPASS
Building #2 West Trench cover; Phone #: ###-#### Internet Inspection Request from: Celinda Winters ok to cover u/g under slab
ELE05-02589 Rough-In Permanent Service7/25/20057/25/20057/25/2005 12:00:00 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Tyler Bowen ric ok p/s u/g n ok