Inspections for the day of: Monday, July 25, 2005.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD04-02988 FIRE-Final Inspection7/25/20057/25/20057/26/2005 8:03:23 AMPFAIL
Repair exit discharge lighting.
FIR05-00282 INSP-Final Inspection7/25/20057/25/20057/25/2005 3:42:02 PMPPASS
Fire sprinkler permit finaled.
FIR05-00417 INSP-Final Inspection7/22/20057/25/20057/25/2005 3:35:15 PMPFAIL
Pendent head in open area is overspaced off adjacent wall.
FIR05-00111 INSP-Final Inspection7/25/20057/25/20057/25/2005 12:45:47 PMPPASS
Fire sprinkler permit finaled, sufficient flow has been verified through the system backflow preventer.
BLD05-00840 FIRE-Sprinkler Rough-in7/25/20057/25/20057/25/2005 11:11:00 AMPCANC
justin ; Phone #: ###-#### Spoke with Justin, this inspection was for a fire wall to be examined by the structural inspector. No fire inspector's signature is required or associated with this project.
BLD05-00700 FIRE-Final Inspection7/22/20057/25/20057/25/2005 9:47:40 AMAPASS
Fire life safety finaled, contractor to remove temporary dust covers on two smoke alarms in common exit corridor immediately.
FIR05-00345 INSP-Final Inspection7/25/20057/25/20057/25/2005 12:00:00 AMAPASS
Fire sprinkler finaled.
BLD04-02153 FIRE-Final Inspection7/25/20057/25/20057/25/2005 12:00:00 AMPPART
Temp. approval per Steve Keuter pending relocation of wall mounted strobe devices to the proper height AFF.
BLD05-00463 FIRE-Final Inspection7/25/20057/25/20057/25/2005 12:00:00 AMPPART
Temp. occupancy granted per Steve Keuter pending relocation of wall mounted strobe devices to the correct height AFF.
FIR05-00306 INSP-Final Inspection7/25/20057/25/20057/25/2005 12:00:00 AMPPASS
Fire sprinkler permit finaled.
FIR05-00294 INSP-Alarm Testing7/25/20057/25/20057/25/2005 12:00:00 AMPFAIL
Provide lock at FACP breaker, provide sign at door to fire control panel room indicating its location.