Inspections for the day of: Tuesday, July 25, 2006.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00182 INSP-Final Inspection7/24/20067/25/20067/26/2006 7:28:22 AMPPASS
Fire alarm permit finaled.
FIR06-00272 INSP-Final Inspection7/24/20067/25/20067/25/2006 1:28:41 PMAFAIL
Descriptors for pull stations do not match point descriptions on the plan, AC power loss is incorrectly identified as NAC trouble, the duct detectors activate a general alarm condition. Need to provide list of signals recieved by remote monitoring of test activity today at next inspection. Notification devices tested okay.
FIR06-00406 INSP-Sprinkler Rough-in/Hydro7/24/20067/25/20067/25/2006 1:23:35 PMAPART
Overhead rough-in is acceptable for cover at the drop ceiling areas, noted DP in the cooler is not installed at this time. Also noted 200 degree heads are installed throughout the entire TI space where only ordinary temp. heads are required per NFPA 13 8.3.2.
MIS06-00186 FIR-Final7/25/20067/25/20067/25/2006 1:20:55 PMPPASS
Fire life safety is satisfactory, field inspection passed. Noted to contact person the building fire extinguishers are due for annual certification next month.
FIR06-00480 INSP-Sprinkler Rough-in/Hydro7/24/20067/25/20067/25/2006 10:14:37 AMAFAIL
Approved plans are not available on site for review as a condition of the permit and requirement for field inspection.