FIR06-00570
| INSP-Final Inspection | 7/24/2007 | 7/25/2007 | 7/25/2007 4:02:11 PM | A | FAIL |
|
|
The phone line troubles do not report correctly. Also need to test the duct smoke detectors.
|
BLD07-00064
| FIRE-Final Inspection | 7/24/2007 | 7/25/2007 | 7/25/2007 4:00:51 PM | A | PASS |
|
|
Life safety is passed.
|
FIR07-00594
| INSP-Sprinkler Rough-in | 7/24/2007 | 7/25/2007 | 7/25/2007 3:59:18 PM | A | PASS |
|
|
Sprinkler piping is ok to cover
|
FIR07-00203
| INSP-Final Inspection | 7/18/2007 | 7/25/2007 | 7/25/2007 1:42:40 PM | P | FAIL |
|
|
Inspection was for the fire pump test. I noted three items that are required per NFPA 20 section 5.12. Drainage, ventilation and emergency lighting. These items were posted on a correction notice in the riser room.
|
FIR06-00664
| INSP-Final Inspection | 7/24/2007 | 7/25/2007 | 7/25/2007 10:53:38 AM | A | FAIL |
|
|
Need forward flush, need sprinkler head in the elevator shaft relocted. The piping in the elevator shaft needs to be relocated due to the elevator guard rail. Signage is needed at the control vavles for the standpipes and at the fdc connection as discussed.
|
FIR06-00708
| INSP-Final Inspection | 7/24/2007 | 7/25/2007 | 7/25/2007 10:48:01 AM | A | FAIL |
|
|
The elevator hat lights were not working in either elevator. The heat detector is too far away from the sprinkler head in the west elevator shaft and the a/v's on the first floor are missing their covers. The elevator testing needs to be started over.
|
FIR07-00237
| INSP-Final Inspection | 7/24/2007 | 7/25/2007 | 7/25/2007 10:45:52 AM | A | FAIL |
|
|
The shell core permit needs finaled first. When that is done this permit can be finaled.
|
FIR07-00103
| INSP-Final Inspection | 7/24/2007 | 7/25/2007 | 7/25/2007 10:44:47 AM | A | FAIL |
|
|
Need the shell core permit finaled first. This permit will be ready to final when that is done.
|