Inspections for the day of: Wednesday, July 25, 2007.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00570 INSP-Final Inspection7/24/20077/25/20077/25/2007 4:02:11 PMAFAIL
The phone line troubles do not report correctly. Also need to test the duct smoke detectors.
BLD07-00064 FIRE-Final Inspection7/24/20077/25/20077/25/2007 4:00:51 PMAPASS
Life safety is passed.
FIR07-00594 INSP-Sprinkler Rough-in7/24/20077/25/20077/25/2007 3:59:18 PMAPASS
Sprinkler piping is ok to cover
FIR07-00203 INSP-Final Inspection7/18/20077/25/20077/25/2007 1:42:40 PMPFAIL
Inspection was for the fire pump test. I noted three items that are required per NFPA 20 section 5.12. Drainage, ventilation and emergency lighting. These items were posted on a correction notice in the riser room.
FIR06-00664 INSP-Final Inspection7/24/20077/25/20077/25/2007 10:53:38 AMAFAIL
Need forward flush, need sprinkler head in the elevator shaft relocted. The piping in the elevator shaft needs to be relocated due to the elevator guard rail. Signage is needed at the control vavles for the standpipes and at the fdc connection as discussed.
FIR06-00708 INSP-Final Inspection7/24/20077/25/20077/25/2007 10:48:01 AMAFAIL
The elevator hat lights were not working in either elevator. The heat detector is too far away from the sprinkler head in the west elevator shaft and the a/v's on the first floor are missing their covers. The elevator testing needs to be started over.
FIR07-00237 INSP-Final Inspection7/24/20077/25/20077/25/2007 10:45:52 AMAFAIL
The shell core permit needs finaled first. When that is done this permit can be finaled.
FIR07-00103 INSP-Final Inspection7/24/20077/25/20077/25/2007 10:44:47 AMAFAIL
Need the shell core permit finaled first. This permit will be ready to final when that is done.