Inspections for the day of: Friday, July 25, 2008.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD08-01265 FIRE-Final Inspection7/25/20087/25/20087/28/2008 8:00:10 AMPNR
Correction notice items are not yet finished per contractor.
FIR08-00210 INSP-Final Inspection7/25/20087/25/20087/28/2008 7:56:33 AMPPASS
Shell fire sprinkler permit okay for final.
FIR08-00357 INSP-Final Inspection7/25/20087/25/20087/25/2008 3:24:01 PMPPASS
Corrections are complete, inspection passed, fire sprinkler permit finaled.
BLD07-03136 FIRE-Final Inspection7/25/20087/25/20087/25/2008 3:22:00 PMPNR
BLD07-03137 FIRE-Final Inspection7/25/20087/25/20087/25/2008 3:21:44 PMPFAIL
Missing one directional exit sign per approved plan annotations, need to repair one non-functional EM light, exit discharge lights at the main entry are not functional.
FIR08-00209 INSP-Final Inspection7/25/20087/25/20087/25/2008 3:09:40 PMPFAIL
Missing a pressure reducing valve at the riser due to gridded overhead system design, one pendent head at the main entry vestibule is obstructed by an adjacent surface mounted light fixture.
FIR08-00182 INSP-Final Inspection7/25/20087/25/20087/25/2008 3:06:43 PMPPASS
UG fire supply line permit finaled.
FIR08-00310 INSP-Final Inspection7/24/20087/25/20087/25/2008 3:06:12 PMAFAIL
Provide correct sample and vent tubes for the duct detectors, FACP and sprinkler monitoring tested okay, the manual pull station relocated and tested while on site.
BLD08-00893 FIRE-Final Inspection7/24/20087/25/20087/25/2008 12:07:10 PMACANC
Gary- fire life safety and sprinkler Phone #: ###-#### Wrong permit number called in for inspection, intended for a different project altogether.
BLD08-00489 FIRE-Final Inspection7/24/20087/25/20087/25/2008 12:03:04 PMAPASS
Fire life safety finaled.
FIR08-00357 INSP-Final Inspection7/24/20087/25/20087/25/2008 11:10:57 AMAFAIL
Two pendents at the new office room are overspaced off an adjacent wall as the small room rule is not applicable for type of construction, contractror agreed to relocate heads while on site.
FIR08-00360 INSP-Final Inspection7/24/20087/25/20087/25/2008 11:07:40 AMAPASS
Correction notice items repaired, inspection passed, permit finaled.
FIR08-00379 INSP-Final Inspection7/24/20087/25/20087/25/2008 11:06:02 AMAPASS
Fire alarm system additions passed field testing, permit finaled.
FIR08-00422 INSP-Sprinkler Rough-in/Hydro7/24/20087/25/20087/25/2008 10:25:05 AMAPART
Noted corrections verified for compliance, rough-in install passed inspection.
FIR08-00495 INSP-Sprinkler Rough-in/Hydro7/24/20087/25/20087/25/2008 10:04:39 AMAPART
OH fire sprinkler system modifications are approved for cover at the drop ceilings within the tenant remodel area.