BLD08-01265
| FIRE-Final Inspection | 7/25/2008 | 7/25/2008 | 7/28/2008 8:00:10 AM | P | NR |
|
|
Correction notice items are not yet finished per contractor.
|
FIR08-00210
| INSP-Final Inspection | 7/25/2008 | 7/25/2008 | 7/28/2008 7:56:33 AM | P | PASS |
|
|
Shell fire sprinkler permit okay for final.
|
FIR08-00357
| INSP-Final Inspection | 7/25/2008 | 7/25/2008 | 7/25/2008 3:24:01 PM | P | PASS |
|
|
Corrections are complete, inspection passed, fire sprinkler permit finaled.
|
BLD07-03136
| FIRE-Final Inspection | 7/25/2008 | 7/25/2008 | 7/25/2008 3:22:00 PM | P | NR |
|
|
|
BLD07-03137
| FIRE-Final Inspection | 7/25/2008 | 7/25/2008 | 7/25/2008 3:21:44 PM | P | FAIL |
|
|
Missing one directional exit sign per approved plan annotations, need to repair one non-functional EM light, exit discharge lights at the main entry are not functional.
|
FIR08-00209
| INSP-Final Inspection | 7/25/2008 | 7/25/2008 | 7/25/2008 3:09:40 PM | P | FAIL |
|
|
Missing a pressure reducing valve at the riser due to gridded overhead system design, one pendent head at the main entry vestibule is obstructed by an adjacent surface mounted light fixture.
|
FIR08-00182
| INSP-Final Inspection | 7/25/2008 | 7/25/2008 | 7/25/2008 3:06:43 PM | P | PASS |
|
|
UG fire supply line permit finaled.
|
FIR08-00310
| INSP-Final Inspection | 7/24/2008 | 7/25/2008 | 7/25/2008 3:06:12 PM | A | FAIL |
|
|
Provide correct sample and vent tubes for the duct detectors, FACP and sprinkler monitoring tested okay, the manual pull station relocated and tested while on site.
|
BLD08-00893
| FIRE-Final Inspection | 7/24/2008 | 7/25/2008 | 7/25/2008 12:07:10 PM | A | CANC |
|
|
Gary- fire life safety and sprinkler Phone #: ###-#### Wrong permit number called in for inspection, intended for a different project altogether.
|
BLD08-00489
| FIRE-Final Inspection | 7/24/2008 | 7/25/2008 | 7/25/2008 12:03:04 PM | A | PASS |
|
|
Fire life safety finaled.
|
FIR08-00357
| INSP-Final Inspection | 7/24/2008 | 7/25/2008 | 7/25/2008 11:10:57 AM | A | FAIL |
|
|
Two pendents at the new office room are overspaced off an adjacent wall as the small room rule is not applicable for type of construction, contractror agreed to relocate heads while on site.
|
FIR08-00360
| INSP-Final Inspection | 7/24/2008 | 7/25/2008 | 7/25/2008 11:07:40 AM | A | PASS |
|
|
Correction notice items repaired, inspection passed, permit finaled.
|
FIR08-00379
| INSP-Final Inspection | 7/24/2008 | 7/25/2008 | 7/25/2008 11:06:02 AM | A | PASS |
|
|
Fire alarm system additions passed field testing, permit finaled.
|
FIR08-00422
| INSP-Sprinkler Rough-in/Hydro | 7/24/2008 | 7/25/2008 | 7/25/2008 10:25:05 AM | A | PART |
|
|
Noted corrections verified for compliance, rough-in install passed inspection.
|
FIR08-00495
| INSP-Sprinkler Rough-in/Hydro | 7/24/2008 | 7/25/2008 | 7/25/2008 10:04:39 AM | A | PART |
|
|
OH fire sprinkler system modifications are approved for cover at the drop ceilings within the tenant remodel area.
|