Inspections for the day of: Monday, July 25, 2011.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00197 INSP-Final Inspection7/22/20117/25/20117/26/2011 3:30:35 PMANR
After hours inspection incompleted due to notification appliances in need of adjustment and lack of access to the server room area.
FIR11-00186 INSP-Final Inspection7/25/20117/25/20117/26/2011 3:25:45 PMAFAIL
Correction items noted during after hours testing include; provide missing notification appliance in the package test chamber room, repair one corridor a/v adjacent to the NN room, relocated MP at one exit door is not finished due to pending work, two device address numbers are inconsistent with stamped plans, SD for door release have been deleted due to scope of work changes, one chamber and two notification devices at life test #2 have been moved. Provide plans reflecting actual scope of work completed including revised locations, addresses, circuts, etc.
FIR11-00327 INSP-Final Inspection7/25/20117/25/20117/26/2011 12:38:20 PMPPART
Final pending hydrostatic testing per NFPA 25 table 5.5.1 component replacement action requirements. Walkthrough completed acceptable.
BLD11-00825 FIRE-Final Inspection7/25/20117/25/20117/25/2011 5:09:51 PMPPASS
Fire life safety inspection completed satisfactory.
FIR11-00360 INSP-Sprinkler Rough-in7/25/20117/25/20117/25/2011 5:08:22 PMPPART
Okay to cover overhead fire sprinkler work at the grid ceilings.
FIR11-00345 INSP-Sprinkler Rough-in7/25/20117/25/20117/25/2011 5:05:38 PMPNR
FIR11-00342 INSP-Sprinkler Rough-in7/22/20117/25/20117/25/2011 11:47:18 AMAPART
Overhead fire sprinkler work at the sheetrock lids and soffits as marked on approved plan set okayed for cover. See dated annotations.
FIR11-00233 INSP-Final Inspection7/25/20117/25/20117/25/2011 11:43:02 AMAPASS
Fire alarm work passed inspection. Permit finaled.
BLD10-01866 FIRE-Final Inspection7/22/20117/25/20117/25/2011 11:31:39 AMAPASS
Life safety finaled.