Inspections for the day of: Monday, July 25, 2011.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00285 INSP-Sprinkler Rough-in7/25/20117/25/20117/25/2011 3:43:59 PMPFAIL
Arrived at job site but found that the piping installation of the underground is being delayed due to problems with other services. Troy said he would reschedule for tomorrow.
BLD11-01619 FIRE-Final Inspection7/25/20117/25/20117/25/2011 2:29:18 PMPFAIL
Provide current inspection for the fire extinguisher and repair the emergency light.
BLD10-01628 FIRE-Final Inspection7/25/20117/25/20117/25/2011 1:45:54 PMPFAIL
Provide a spill kit for the batteries and signage as per the review comments.
FIR11-00204 INSP-Sprinkler Rough-in7/22/20117/25/20117/25/2011 1:45:11 PMAPASS
Sprinkler piping can be covered. The branchline tie-ins are not completed but will be verified from the mechanical mezzanine at the final inspection.
FIR11-00179 INSP-Sprinkler Rough-in7/22/20117/25/20117/25/2011 1:44:46 PMAPASS
Sprinkler piping can be covered. The branchline tie-ins are not completed but will be verified from the mechanical mezzanine at the final inspection. Also sprinkler coverage will be required under the duct work on the mechanical mezzanine as discussed.
FIR11-00272 INSP-Final Inspection7/22/20117/25/20117/25/2011 9:01:20 AMAPASS
permit finaled
FIR11-00080 INSP-Final Inspection7/22/20117/25/20117/25/2011 9:00:52 AMAPASS
Permit finaled