Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00662 INSP-Alarm Testing7/24/20127/25/20127/25/2012 3:48:44 PMPCANC
Cancel per Matt Casey due to flooring being installed and elevator problems.
FIR12-00382 INSP-Final Inspection7/25/20127/25/20127/25/2012 3:11:38 PMPPASS
Permit finaled
BLD11-02500 FIRE-Final Inspection7/25/20127/25/20127/25/2012 3:11:03 PMPFAIL
Provide address, remove the exit sign as discussed and provide revised building plans showing the fence/storage area on the west side of the building.
FIR12-00382 INSP-Sprinkler Rough-in7/25/20127/25/20127/25/2012 3:09:06 PMPPASS
Rough-in passed.
BLD12-00294 FIRE-Final Inspection7/24/20127/25/20127/25/2012 11:08:08 AMAPASS
life safety passed
FIR12-00033 INSP-Alarm Testing7/24/20127/25/20127/25/2012 10:11:33 AMADONE
Todays test was for the first floor lobby/desk remodeled area. The list of corrections needed are: the manual pull station needs to be relocated from behind the handicap partion, smoke detector in Corridor 105 (by electrical room) is less than 3' from supply diffuser, the audible portion of the fire alarm system does not sync. between buildings 1 and 2, all of phase 1 work needs to be completed including the total area coverage of smoke detectors in the Lobby area, access panels need to be provided as per IMC 607.4 to the louvers of the fire/smoke dampers, the ceiling mount strobe in the Foothills Conference Room is overspaced from the entry doors. Horn/strobes were tested and the new pull station at the south exit doors was tested. None of the smoke detectors or the fire/smoke dampers were tested. One overspaced strobe and two smoke detectors located too close to hvac were corrected while I waited. During the testing of the second floor ceiling mounted strobe I noted multiple audible signals and possible sync. problems.