Inspections for the day of: Friday, July 25, 2014.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE14-02024 Final7/25/20147/25/20147/25/2014 2:35:35 PMPPASS
Call if you could please to make sure we can get you in.
Thanks
Eddy ###-#### Phone #: ###-#### >> Inspection requested via web by Eddy Udry Final ok
ELE14-02024 Electrical Rough-In7/25/20147/25/20147/25/2014 2:35:29 PMPPASS
Call if you could please to make sure we can get you in.
Thanks
Eddy ###-#### Phone #: ###-#### >> Inspection requested via web by Eddy Udry Furnace and AC rough in ok.
ELE14-02024 Electrical Rough-In7/25/20147/25/20147/25/2014 2:27:03 PMPPASS
Call if you could please to make sure we can get you in.
Thanks
Eddy ###-#### Phone #: ###-#### >> Furnace and AC rough in ok cover
ELE13-03157 Final7/25/20147/25/20147/25/2014 2:02:21 PMPFAIL
Phone #: ###-#### >> Inspection requested via web by kendall bender 210.8- All 15 and 20 amp 120 volt receptical outlets shall have GFCI protection.
110.26- Minimum work space of 30" wide and 36" deep shall beclear of vegetation in front of meter panel combo.
314.17- NM cable sheathing shall enter box by minimum of 1/4". Bay 4 opener outlet.
408-4- Circuit directory shall be complete.
ELE14-02033 Temporary Service7/25/20147/25/20147/25/2014 1:16:42 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Darryn Coburn t/s u/g n ok
ELE12-01528 ELE-Aging Inspection7/25/20147/25/20147/25/2014 11:14:10 AM DONE
Called contracotr to check into address and schedule
ELE10-02067 ELE-Aging Inspection7/25/20147/25/20147/25/2014 11:03:20 AM DONE
Waiting for UL listing verification
ELE12-01591 ELE-Aging Inspection7/25/20147/25/20147/25/2014 10:53:03 AM DONE
Drove by
ELE12-01591 Final7/25/20147/25/20147/25/2014 10:52:30 AMPPASS
Final ok
MIS14-00162 ELE-Conference7/18/20147/25/20147/25/2014 10:27:45 AMADONE
Reinspect unit for corrections compiance. Spoke with owner of bldg and explained the over heating issue. They are getting bids to correct electric issues. Tenant in unit A has moved out. Due to reduced demand at this time main breaker feeding 7155 is cool to touch as well as sub panel feeders. Will re check in 2 weeks.
ELE14-01272 Final7/24/20147/25/20147/25/2014 10:06:46 AMAPASS
call for code Phone #: ###-#### >> Inspection requested via web by Neal Rumsey Final ok
ELE14-02016 Final7/24/20147/25/20147/25/2014 9:39:54 AMAPASS
Please contact Greg Atrian if you have any questions Phone #: ###-#### >> Inspection requested via web by Stacie Tasker Final ok
ELE14-02016 Electrical Rough-In7/25/20147/25/20147/25/2014 9:14:49 AMPPASS
Please contact Greg Atrian if you have any questions Phone #: ###-#### >> Inspection requested via web by Stacie Tasker Receptical outlet addition for data rough in ok
ELE14-01158 Electrical Rough-In7/24/20147/25/20147/25/2014 9:07:02 AMAPASS
We are requesting a rough-in inspection for the storage areas on the canopy project for tomorrow 7/25/14 in the AM. Our onsite contact is Bryant Adams @ ###-####. Thank you. Phone #: ###-#### >> Inspection requested via web by Clint Tate Canopy area walls and hard lid rough in ok cover
ELE14-02017 Electrical Rough-In7/24/20147/25/20147/25/2014 8:44:08 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Harvey Reyna Rough in ok cover