ELE14-02024
| Final | 7/25/2014 | 7/25/2014 | 7/25/2014 2:35:35 PM | P | PASS |
|
|
Call if you could please to make sure we can get you in. Thanks Eddy ###-#### Phone #: ###-#### >> Inspection requested via web by Eddy Udry Final ok
|
ELE14-02024
| Electrical Rough-In | 7/25/2014 | 7/25/2014 | 7/25/2014 2:35:29 PM | P | PASS |
|
|
Call if you could please to make sure we can get you in. Thanks Eddy ###-#### Phone #: ###-#### >> Inspection requested via web by Eddy Udry Furnace and AC rough in ok.
|
ELE14-02024
| Electrical Rough-In | 7/25/2014 | 7/25/2014 | 7/25/2014 2:27:03 PM | P | PASS |
|
|
Call if you could please to make sure we can get you in. Thanks Eddy ###-#### Phone #: ###-#### >> Furnace and AC rough in ok cover
|
ELE13-03157
| Final | 7/25/2014 | 7/25/2014 | 7/25/2014 2:02:21 PM | P | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by kendall bender 210.8- All 15 and 20 amp 120 volt receptical outlets shall have GFCI protection. 110.26- Minimum work space of 30" wide and 36" deep shall beclear of vegetation in front of meter panel combo. 314.17- NM cable sheathing shall enter box by minimum of 1/4". Bay 4 opener outlet. 408-4- Circuit directory shall be complete.
|
ELE14-02033
| Temporary Service | 7/25/2014 | 7/25/2014 | 7/25/2014 1:16:42 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Darryn Coburn t/s u/g n ok
|
ELE12-01528
| ELE-Aging Inspection | 7/25/2014 | 7/25/2014 | 7/25/2014 11:14:10 AM | | DONE |
|
|
Called contracotr to check into address and schedule
|
ELE10-02067
| ELE-Aging Inspection | 7/25/2014 | 7/25/2014 | 7/25/2014 11:03:20 AM | | DONE |
|
|
Waiting for UL listing verification
|
ELE12-01591
| ELE-Aging Inspection | 7/25/2014 | 7/25/2014 | 7/25/2014 10:53:03 AM | | DONE |
|
|
Drove by
|
ELE12-01591
| Final | 7/25/2014 | 7/25/2014 | 7/25/2014 10:52:30 AM | P | PASS |
|
|
Final ok
|
MIS14-00162
| ELE-Conference | 7/18/2014 | 7/25/2014 | 7/25/2014 10:27:45 AM | A | DONE |
|
|
Reinspect unit for corrections compiance. Spoke with owner of bldg and explained the over heating issue. They are getting bids to correct electric issues. Tenant in unit A has moved out. Due to reduced demand at this time main breaker feeding 7155 is cool to touch as well as sub panel feeders. Will re check in 2 weeks.
|
ELE14-01272
| Final | 7/24/2014 | 7/25/2014 | 7/25/2014 10:06:46 AM | A | PASS |
|
|
call for code Phone #: ###-#### >> Inspection requested via web by Neal Rumsey Final ok
|
ELE14-02016
| Final | 7/24/2014 | 7/25/2014 | 7/25/2014 9:39:54 AM | A | PASS |
|
|
Please contact Greg Atrian if you have any questions Phone #: ###-#### >> Inspection requested via web by Stacie Tasker Final ok
|
ELE14-02016
| Electrical Rough-In | 7/25/2014 | 7/25/2014 | 7/25/2014 9:14:49 AM | P | PASS |
|
|
Please contact Greg Atrian if you have any questions Phone #: ###-#### >> Inspection requested via web by Stacie Tasker Receptical outlet addition for data rough in ok
|
ELE14-01158
| Electrical Rough-In | 7/24/2014 | 7/25/2014 | 7/25/2014 9:07:02 AM | A | PASS |
|
|
We are requesting a rough-in inspection for the storage areas on the canopy project for tomorrow 7/25/14 in the AM. Our onsite contact is Bryant Adams @ ###-####. Thank you. Phone #: ###-#### >> Inspection requested via web by Clint Tate Canopy area walls and hard lid rough in ok cover
|
ELE14-02017
| Electrical Rough-In | 7/24/2014 | 7/25/2014 | 7/25/2014 8:44:08 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Harvey Reyna Rough in ok cover
|