Inspections for the day of: Friday, July 25, 2014.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE14-01808 Final7/25/20147/25/20147/25/2014 2:03:29 PMPPASS
Jerry Phone #: ###-#### ok final
ELE14-01807 Final7/18/20147/25/20147/25/2014 1:56:27 PMPPASS
>> Inspection requested via web by Louis Keller ok final
ELE14-01016 Electrical Rough-In7/25/20147/25/20147/25/2014 1:38:27 PMPFAIL
kelly Phone #: ###-#### met owner, had him write down violations, told would list on-line, shall tighten grounding electrode conductor on concrete encased electrode, shall tie grounds together in boxes for make-up, shall provide nailplates, shall staple wiring at panel, shall not staple nm on edge, shall not exceed box fill, shall not have receptacle on small appliance branch circuit at bottom of stairs, will fix and recall
ELE14-02031 Electrical Rough-In7/25/20147/25/20147/25/2014 12:30:11 PMPPASS
Uffer inspection Phone #: ###-#### >> Inspection requested via web by Stacie Tasker ok pour concrete encased electrode
ELE14-02019 Temporary Service7/24/20147/25/20147/25/2014 11:45:39 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Bob Glenn t/s u/g n ok
ELE14-01333 Final7/23/20147/25/20147/25/2014 11:02:46 AMAPASS
Garage code 1979E Phone #: ###-#### >> Inspection requested via web by Alan Lusk ok final
ELE14-01943 Rough-In Permanent Service7/24/20147/25/20147/25/2014 9:55:07 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Bob Glenn ri ok, p/s u/g n ok
ELE14-01639 Electrical Rough-In7/24/20147/25/20147/25/2014 9:12:54 AMAPASS
Floor heat - Mike Phone #: ###-#### ok cover floor heat
ELE14-01026 Final7/24/20147/25/20147/25/2014 8:43:48 AMAPASS
Lock box is on the right side of the front door, combo is 2343 Phone #: ###-#### >> Inspection requested via web by Brad Girard ok final