FIR13-00612
| INSP-Sprinkler Rough-in | 7/25/2014 | 7/25/2014 | 7/25/2014 3:30:48 PM | P | CANC |
|
|
No approved plans on site so Robert is going to reschedule for monday with a flush.
|
BLD14-00038
| FIRE-Final Inspection | 7/24/2014 | 7/25/2014 | 7/25/2014 3:20:32 PM | A | FAIL |
|
|
Life safety in Maternity area will be ok to sign off when the fire alarm is passed in this area.
|
FIR14-00439
| INSP-Sprinkler Rough-in | 7/24/2014 | 7/25/2014 | 7/25/2014 2:19:45 PM | P | PASS |
|
|
Sprinkler rough-in passed. Piping can be covered. The flex-heads are not locked down yet and final spacing will need to be verified.
|
BLD14-00895
| FIRE-Final Inspection | 7/25/2014 | 7/25/2014 | 7/25/2014 2:18:23 PM | P | PART |
|
|
Life safety passed for second floor work only and the exiting to the first floor. Need the project related fire alarm approved.
|
FIR14-00438
| INSP-Alarm Testing | 7/24/2014 | 7/25/2014 | 7/25/2014 2:17:13 PM | P | DONE |
|
|
Second floor fire alarm complete. Plan modifications will need to be approved showing the location of the new NAC panel, smoke detector, change in trigger point and the change of notification devices.
|
BLD14-01701
| FIRE-Final Inspection | 7/17/2014 | 7/25/2014 | 7/25/2014 12:57:01 PM | A | PASS |
|
|
life safety passed
|
BLD14-01808
| FIRE-Final Inspection | 7/25/2014 | 7/25/2014 | 7/25/2014 12:42:21 PM | P | PASS |
|
|
life safety passed
|
FIR14-00524
| INSP-Sprinkler Rough-in | 7/24/2014 | 7/25/2014 | 7/25/2014 10:16:52 AM | A | PASS |
|
|
Underground supply piping is ok to cover.
|
BLD13-02595
| FIRE-Final Inspection | 7/24/2014 | 7/25/2014 | 7/25/2014 10:04:07 AM | A | FAIL |
|
|
Repair exit signs, provide indicator on the main exit door. Provide fire extinguisher on the upper level. Provide listed for the enviroment exit discharge lights. Provide building address
|
FIR14-00285
| INSP-Sprinkler Rough-in/Hydro | 7/24/2014 | 7/25/2014 | 7/25/2014 9:55:12 AM | A | PASS |
|
|
The overhead hydro test passed. Rough-in inspection for overhead piping passed. Piping can be covered.
|
FIR14-00274
| INSP-Alarm Testing | 7/24/2014 | 7/25/2014 | 7/25/2014 9:07:42 AM | A | FAIL |
|
|
The fire sprinkler contractor did not call for a final for his items and is needed to test the tamper and pressure switches on the new dry systems. No inspection performed.
|
BLD14-00714
| FIRE-Final Inspection | 7/25/2014 | 7/25/2014 | 7/25/2014 9:06:22 AM | A | FAIL |
|
|
Called Doug and left voice message I was on the way. No contact made at project site. Performed quick inspection and found exit signs missing, one missing fire extinguisher and the new wall in the Break Room has cause sprinkler pendants to be overspaced in the Engineering Room
|
FIR14-00523
| INSP-Final Inspection | 7/24/2014 | 7/25/2014 | 7/25/2014 9:04:09 AM | A | PASS |
|
|
Permit finaled
|
FIR14-00210
| INSP-Alarm Testing | 7/25/2014 | 7/25/2014 | 7/25/2014 8:01:08 AM | P | CANC |
|
|
Call for access Phone #: 2089411846 >> Inspection requested via mobile web by Brian A Inspection cancelled via mobile web on Friday, July 25, 2014.
|
FIR14-00137
| INSP-Final Inspection | 7/24/2014 | 7/25/2014 | 7/25/2014 7:53:28 AM | A | PASS |
|
|
permit finaled
|