Inspections for the day of: Friday, July 25, 2014.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR13-00612 INSP-Sprinkler Rough-in7/25/20147/25/20147/25/2014 3:30:48 PMPCANC
No approved plans on site so Robert is going to reschedule for monday with a flush.
BLD14-00038 FIRE-Final Inspection7/24/20147/25/20147/25/2014 3:20:32 PMAFAIL
Life safety in Maternity area will be ok to sign off when the fire alarm is passed in this area.
FIR14-00439 INSP-Sprinkler Rough-in7/24/20147/25/20147/25/2014 2:19:45 PMPPASS
Sprinkler rough-in passed. Piping can be covered. The flex-heads are not locked down yet and final spacing will need to be verified.
BLD14-00895 FIRE-Final Inspection7/25/20147/25/20147/25/2014 2:18:23 PMPPART
Life safety passed for second floor work only and the exiting to the first floor. Need the project related fire alarm approved.
FIR14-00438 INSP-Alarm Testing7/24/20147/25/20147/25/2014 2:17:13 PMPDONE
Second floor fire alarm complete. Plan modifications will need to be approved showing the location of the new NAC panel, smoke detector, change in trigger point and the change of notification devices.
BLD14-01701 FIRE-Final Inspection7/17/20147/25/20147/25/2014 12:57:01 PMAPASS
life safety passed
BLD14-01808 FIRE-Final Inspection7/25/20147/25/20147/25/2014 12:42:21 PMPPASS
life safety passed
FIR14-00524 INSP-Sprinkler Rough-in7/24/20147/25/20147/25/2014 10:16:52 AMAPASS
Underground supply piping is ok to cover.
BLD13-02595 FIRE-Final Inspection7/24/20147/25/20147/25/2014 10:04:07 AMAFAIL
Repair exit signs, provide indicator on the main exit door. Provide fire extinguisher on the upper level. Provide listed for the enviroment exit discharge lights. Provide building address
FIR14-00285 INSP-Sprinkler Rough-in/Hydro7/24/20147/25/20147/25/2014 9:55:12 AMAPASS
The overhead hydro test passed. Rough-in inspection for overhead piping passed. Piping can be covered.
FIR14-00274 INSP-Alarm Testing7/24/20147/25/20147/25/2014 9:07:42 AMAFAIL
The fire sprinkler contractor did not call for a final for his items and is needed to test the tamper and pressure switches on the new dry systems. No inspection performed.
BLD14-00714 FIRE-Final Inspection7/25/20147/25/20147/25/2014 9:06:22 AMAFAIL
Called Doug and left voice message I was on the way. No contact made at project site. Performed quick inspection and found exit signs missing, one missing fire extinguisher and the new wall in the Break Room has cause sprinkler pendants to be overspaced in the Engineering Room
FIR14-00523 INSP-Final Inspection7/24/20147/25/20147/25/2014 9:04:09 AMAPASS
Permit finaled
FIR14-00210 INSP-Alarm Testing7/25/20147/25/20147/25/2014 8:01:08 AMPCANC
Call for access Phone #: 2089411846 >> Inspection requested via mobile web by Brian A Inspection cancelled via mobile web on Friday, July 25, 2014.
FIR14-00137 INSP-Final Inspection7/24/20147/25/20147/25/2014 7:53:28 AMAPASS
permit finaled