Inspections for the day of: Tuesday, July 25, 2017.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorMark Moncarr
TitleELE-INSPECTOR
Phone #685-9023
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-02390 Electrical Rough-In7/25/20177/25/20177/25/2017 1:44:20 PMPPASS
Electrical rough Building D 3rd and 4th floor Phone #: ###-#### Inspection requested via web by Bob Stephens Ok cover floors 3-4
ELE17-00806 Final7/25/20177/25/20177/25/2017 1:24:10 PMPFAIL
corey Phone #: ###-#### All areas in question are considered Category 3 Basic Care Space. Category 1 does not require GFI protection. 517.21 states this. All other Category classifications require GFI protection as per 517.21 commentary that reverts to 210.8(B), GFI protection for personnel.
ELE17-01697 Electrical Rough-In7/24/20177/25/20177/25/2017 12:06:34 PMPPASS
The lock box code is 8068. If you have any questions please call Bobby ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clay Morgan Ok cover
ELE17-02347 Final7/25/20177/25/20177/25/2017 11:43:09 AMPPASS
unoccupied residence, key under rock on porch. replaced service, 18'' clearance for traffic in ally. feeder to Range with 4 wire. No laundry. Installed GFCI in bathroom and kitchen. Grounding. Phone #: ###-#### Inspection requested via web by Steve Blackmer ok final
ELE17-02347 Permanent Service7/25/20177/25/20177/25/2017 11:41:46 AMPPASS
unoccupied residence, key under rock on porch. replaced service, 18'' clearance for traffic in ally. feeder to Range with 4 wire. No laundry. Installed GFCI in bathroom and kitchen. Grounding. Phone #: ###-#### Inspection requested via web by Steve Blackmer p/s o/h rec ok
ELE17-02366 Final7/22/20177/25/20177/25/2017 10:48:04 AMAPASS
Phone #: ###-#### Inspection requested via web by Jake Weaver Ok final
ELE16-02623 Final7/24/20177/25/20177/25/2017 9:58:59 AMAPASS
units 209 , 210, 211 , 212 , 309 , 310 , 311 , 312, 1411 ,com room , and TI Last of the Finals Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty Ok final
ELE17-01350 Conference7/24/20177/25/20177/25/2017 9:15:43 AMADONE
Mike Phone #: ###-#### Discussed the use of ground screws in all metal boxes. Tamper res on inside and Weather res on outside. Interior finish will be OSB, surfaced mounted MC and metal boxes.
ELE17-02124 Permanent Service7/24/20177/25/20177/25/2017 8:53:23 AMAPASS
Service Phone #: ###-#### Inspection requested via web by Kevin Burke p/s o/h n ok
ELE13-02510 ELE-Aging Inspection7/25/20177/25/20177/25/2017 7:55:25 AM DONE
Contact me at ###-#### for progress on job.