Inspections for the day of: Wednesday, July 25, 2018.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-02007 Final7/24/20187/25/20187/25/2018 2:01:57 PMPPASS
Reinspection of closet luminaire.

?+1 ###-####?

Phone #: Inspection requested via web by Garrett Collins Final ok
ELE17-02862 Electrical Rough-In7/25/20187/25/20187/25/2018 1:49:21 PMPPASS
units 115 , 110 , 111 and dog wash Phone #: ###-#### Inspection requested via web by Tom Betty
Rooms noted rough in ok cover
ELE18-01998 Electrical Rough-In7/24/20187/25/20187/25/2018 1:34:19 PMPPASS
Ceiling rough-in for cover. Please call Darrin (###-####) with questions. Phone #: ###-#### Inspection requested via web by Scott Campbell
Ceiling rough in ok cover
ELE18-02820 Temporary Service7/25/20187/25/20187/25/2018 12:32:01 PMPPASS
Service Inspection Phone #: ###-#### Inspection requested via web by Bryan Atkins t/s o/h n ok
ELE18-01320 Final7/25/20187/25/20187/25/2018 10:58:03 AMAPASS
homeowner will be home all morning. Please call if you have any questions thank you Shaun Phone #: ###-#### Inspection requested via web by Shaun Kirkman Final ok
ELE18-01201 Final7/24/20187/25/20187/25/2018 10:19:54 AMAFAIL
4324 Garage Code Phone #: ###-#### Inspection requested via web by Darryn Coburn
110.3- Not all circuits operating, upper level stair not working and upper landing. Buried box.
250.148- Where conductors are spliced in a box all equipment grounds shall be connected together by approved means. Island 3 gang.
314.17- Where NM cable enters a non metallic box the sheathing shall enter box a minimum of 1/4". Island 3 gang.
314.20- Where box is mounted in a combustible material it shall be flush or have extension rings installed.
*Job not checked out prior to inspection, reinspection fee assessed.
ELE18-01200 Final7/24/20187/25/20187/25/2018 10:13:31 AMAFAIL
Garage Code 4224 Phone #: ###-#### Inspection requested via web by Darryn Coburn
250.148- Where conductors are spliced in a box all equipment grounds shall be connected together by approved means. Island 3 gang.
314.20- Where box is recessed more than 1/4" in not combustable materials a extension ring shall be installed. Boxes back of garage.
ELE17-02183 Final7/24/20187/25/20187/25/2018 8:53:37 AMAPASS
Call Mike Cole with any questions Phone #: ###-#### Inspection requested via web by Bonnie Page Final ok
ELE18-01998 Electrical Rough-In7/24/20187/25/20187/24/2018 1:25:59 PMACANC
Rough-in Ceiling for Cover. Please call Darrin (###-####) with questions. Phone #: ###-#### >> Inspection requested via web by Scott Campbell Inspection cancelled from web by: Scott Campbell