ELE18-02007
| Final | 7/24/2018 | 7/25/2018 | 7/25/2018 2:01:57 PM | P | PASS |
|
|
Reinspection of closet luminaire.
?+1 ###-####?
Phone #: Inspection requested via web by Garrett Collins Final ok
|
ELE17-02862
| Electrical Rough-In | 7/25/2018 | 7/25/2018 | 7/25/2018 1:49:21 PM | P | PASS |
|
|
units 115 , 110 , 111 and dog wash Phone #: ###-#### Inspection requested via web by Tom Betty Rooms noted rough in ok cover
|
ELE18-01998
| Electrical Rough-In | 7/24/2018 | 7/25/2018 | 7/25/2018 1:34:19 PM | P | PASS |
|
|
Ceiling rough-in for cover. Please call Darrin (###-####) with questions. Phone #: ###-#### Inspection requested via web by Scott Campbell Ceiling rough in ok cover
|
ELE18-02820
| Temporary Service | 7/25/2018 | 7/25/2018 | 7/25/2018 12:32:01 PM | P | PASS |
|
|
Service Inspection Phone #: ###-#### Inspection requested via web by Bryan Atkins t/s o/h n ok
|
ELE18-01320
| Final | 7/25/2018 | 7/25/2018 | 7/25/2018 10:58:03 AM | A | PASS |
|
|
homeowner will be home all morning. Please call if you have any questions thank you Shaun Phone #: ###-#### Inspection requested via web by Shaun Kirkman Final ok
|
ELE18-01201
| Final | 7/24/2018 | 7/25/2018 | 7/25/2018 10:19:54 AM | A | FAIL |
|
|
4324 Garage Code Phone #: ###-#### Inspection requested via web by Darryn Coburn 110.3- Not all circuits operating, upper level stair not working and upper landing. Buried box. 250.148- Where conductors are spliced in a box all equipment grounds shall be connected together by approved means. Island 3 gang. 314.17- Where NM cable enters a non metallic box the sheathing shall enter box a minimum of 1/4". Island 3 gang. 314.20- Where box is mounted in a combustible material it shall be flush or have extension rings installed. *Job not checked out prior to inspection, reinspection fee assessed.
|
ELE18-01200
| Final | 7/24/2018 | 7/25/2018 | 7/25/2018 10:13:31 AM | A | FAIL |
|
|
Garage Code 4224 Phone #: ###-#### Inspection requested via web by Darryn Coburn 250.148- Where conductors are spliced in a box all equipment grounds shall be connected together by approved means. Island 3 gang. 314.20- Where box is recessed more than 1/4" in not combustable materials a extension ring shall be installed. Boxes back of garage.
|
ELE17-02183
| Final | 7/24/2018 | 7/25/2018 | 7/25/2018 8:53:37 AM | A | PASS |
|
|
Call Mike Cole with any questions Phone #: ###-#### Inspection requested via web by Bonnie Page Final ok
|
ELE18-01998
| Electrical Rough-In | 7/24/2018 | 7/25/2018 | 7/24/2018 1:25:59 PM | A | CANC |
|
|
Rough-in Ceiling for Cover. Please call Darrin (###-####) with questions. Phone #: ###-#### >> Inspection requested via web by Scott Campbell Inspection cancelled from web by: Scott Campbell
|