FIR19-00007
| INSP-Final Inspection | 7/25/2019 | 7/25/2019 | 7/25/2019 2:32:25 PM | P | FAIL |
|
|
No inspection performed. Fitter did not have means to flow water through an orfice to match the installed sprinkler pendants. No other items looked at. Will need to reschedule.
Call Anthony to coordinate time before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
BLD18-01631
| FIRE-Conference | 7/25/2019 | 7/25/2019 | 7/25/2019 2:09:41 PM | P | DONE |
|
|
Carrie and I went over her life safety comments
|
BLD19-01243
| FIRE-Final Inspection | 7/24/2019 | 7/25/2019 | 7/25/2019 2:08:42 PM | P | FAIL |
|
|
Provide emergency lighting as discussed and mount the fire extinguishers as discussed.
tOD Phone #: ###-####
|
FIR19-00482
| INSP-Alarm Testing | 7/24/2019 | 7/25/2019 | 7/25/2019 1:40:47 PM | P | FAIL |
|
|
The notification (horns) did not sync as required per NFPA 72 18.4.2.4. Need as-builts approved. Thanks for coming out yesterday Troy. I apologize for the inefficiency. I (We) know better than to waist your time. Learned something new about the spare Simplex NAC output used as a trigger. Call me when you feel you can make it. Thanks Mike Phone #: ###-#### Inspection requested via web by Michael Timmerman
|
BLD18-03923
| FIRE-Final Inspection | 7/24/2019 | 7/25/2019 | 7/25/2019 1:39:47 PM | P | PART |
|
|
Life safety is being given a partial for the remodeled office area behind the new check-in counter. Brandon Phone #: ###-####
|
BLD19-02773
| FIRE-Final Inspection | 7/25/2019 | 7/25/2019 | 7/25/2019 1:37:21 PM | P | PASS |
|
|
Life safety passed
|
NAF18-00124
| INSP-Sprinkler Rough-in/Hydro | 7/24/2019 | 7/25/2019 | 7/25/2019 10:33:04 AM | A | PASS |
|
|
The hydro tests for both overhead wet systems witnessed with no pressure loss. Call prior to going Phone #: 2088801974 >> Inspection requested via mobile web by Tyler
|
BLD19-02773
| FIRE-Final Inspection | 7/25/2019 | 7/25/2019 | 7/25/2019 10:29:54 AM | A | FAIL |
|
|
Provide drawings and small documents, repair or remove the non-functional exit signs
|
BLD19-02773
| FIRE-Final Inspection | 7/24/2019 | 7/25/2019 | 7/25/2019 8:05:14 AM | A | FAIL |
|
|
Called twice. Went to project site. No one was there. No inspection performed.
Lyndsey- call for access Phone #: ###-####
|
FIR19-00375
| INSP-Final Inspection | 7/24/2019 | 7/25/2019 | 7/24/2019 2:55:43 PM | A | PASS |
|
|
Permit finaled
Troy - Per our phone conversation on 7/24, this has been scheduled per your verbal..
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
BLD18-03923
| FIRE-Final Inspection | 7/24/2019 | 7/25/2019 | 7/24/2019 2:52:32 PM | A | PART |
|
|
Life safety is passed for the Lobby area but not the back office area. Per discussion emergency lighting will be required for the existing lobby prior to a final sign off just as it is being required at the bottom of both stairwells.
Brandon Phone #: ###-####
|