ELE02-02308
| Electrical Rough-In | 7/24/2002 | 7/26/2002 | 7/26/2002 12:00:00 AM | A | FAIL |
|
|
###-#### cor. posted called left message 300.4 nail pates and 11/4 300.11(C) shall not tie wrap cables together
for support 330.30(C) strap cable within 12 inches of boxes and panels 7/26/2002 1:51:24 PM
|
ELE01-02309
| Final | 7/25/2002 | 7/26/2002 | 7/26/2002 12:00:00 AM | A | PASS |
|
|
JERRY ###-#### ok 7/26/2002 10:47:20 AM
|
ELE02-02320
| Final | 7/25/2002 | 7/26/2002 | 7/26/2002 12:00:00 AM | A | FAIL |
|
|
THIS IS FOR A PUMP \\###-#### cor.posted called see PM#ELE02-02319 for correction info 7/26/2002 12:24:24 PM
|
ELE02-02319
| Final | 7/25/2002 | 7/26/2002 | 7/26/2002 12:00:00 AM | A | FAIL |
|
|
###-#### ben cor. posted 240.24(D) sub panel not allowed in closet under stairs, 300.10 loose locknuts, and fittings bond bushings for r e washers, 110.3(B) use listed fittings for flex, and no plumbing fittings to be used 310.16 shall provide proper overcurrent protection for #12 and #14 awg , 240.21 (2) shall terminate tap from panel bus to sub panel in breaker,or fuses, 250.24(A)(5) isolate grds and nuetrals at sub panel and pump disconnect 200.7 shall ID white wire used as phase conductor, 344.46 bushings for rigid nipples. 348.30 secure flex 7/26/2002 12:40:25 PM
|
ELE02-01696
| Permanent Service | 7/25/2002 | 7/26/2002 | 7/26/2002 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 07/25/2002 at 12:50:55. Contact: ###-####.
p/s u/g new ok 7/25/2002 3:33:24 PM
|
ELE02-02215
| Electrical Rough-In | 7/25/2002 | 7/26/2002 | 7/26/2002 12:00:00 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 07/25/2002 at 13:55:21. Contact: ###-####. walls ok 7/26/2002 1:06:50 PM
|
ELE02-02323
| Permanent Service | 7/25/2002 | 7/26/2002 | 7/26/2002 12:00:00 AM | A | FAIL |
|
|
CALL FIRST TO MEET MARV ###-#### set up meeting at 9:00 am waited 10 min. they did not show up, they ca;lled I told I would meet them they did not want to wait 7/26/2002 12:44:29 PM
|
ELE01-03617
| Electrical Rough-In | 7/25/2002 | 7/26/2002 | 7/26/2002 12:00:00 AM | P | PART |
|
|
Scheduled by a contractor via Hello! on 07/25/2002 at 14:48:11. Contact: ###-####. u/g for parking lot lights 7/26/2002 3:37:03 PM
|
ELE02-02340
| Electrical Rough-In | 7/26/2002 | 7/26/2002 | 7/26/2002 12:00:00 AM | P | FAIL |
|
|
r/i david ###-#### 230.28 guy kit, 250.53(D) 2 grd rods, proper space apart note even from phone grd rod, 250.64 (E) G E C continuous from point of attachment to cabinet cor. posted called 7/26/2002 4:26:09 PM
|
ELE02-01832
| Rough-In Permanent Service | 7/26/2002 | 7/26/2002 | 7/26/2002 12:00:00 AM | P | FAIL |
|
|
chris cover ; Phone #: ###-#### cor. and 45.00 reinspection fee due called 110.12 seal ko s, 310.16 shall provide proper sized branch circuit wiring to fixtures that are daisy chained, shall have all make up of wires at boxes complete before inspection is requested 7/26/2002 5:54:28 PM
|
ELE02-01775
| Final | 7/26/2002 | 7/26/2002 | 7/26/2002 12:00:00 AM | P | PASS |
|
|
###-#### karen ok 7/26/2002 6:45:24 PM
|
ELE02-02280
| Permanent Service | 7/26/2002 | 7/26/2002 | 7/26/2002 12:00:00 AM | P | PASS |
|
|
###-#### p/s u/g new ok 7/26/2002 6:25:52 PM
|
ELE02-02343
| Rough-In Permanent Service | 7/26/2002 | 7/26/2002 | 7/26/2002 12:00:00 AM | P | PASS |
|
|
PAT ###-#### ok 7/29/2002 11:35:02 AM
|