Inspections for the day of: Friday, July 26, 2002.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE02-02308 Electrical Rough-In7/24/20027/26/20027/26/2002 12:00:00 AMAFAIL
###-#### cor. posted called left message 300.4 nail pates and 11/4 300.11(C) shall not tie wrap cables together
for support 330.30(C) strap cable within 12 inches of boxes and panels 7/26/2002 1:51:24 PM
ELE01-02309 Final7/25/20027/26/20027/26/2002 12:00:00 AMAPASS
JERRY ###-#### ok 7/26/2002 10:47:20 AM
ELE02-02320 Final7/25/20027/26/20027/26/2002 12:00:00 AMAFAIL
THIS IS FOR A PUMP \\###-#### cor.posted called see PM#ELE02-02319 for correction info 7/26/2002 12:24:24 PM
ELE02-02319 Final7/25/20027/26/20027/26/2002 12:00:00 AMAFAIL
###-#### ben cor. posted 240.24(D) sub panel not allowed in closet under stairs, 300.10 loose locknuts, and fittings bond bushings for r e washers, 110.3(B) use listed fittings for flex, and no plumbing fittings to be used 310.16 shall provide proper overcurrent protection for #12 and #14 awg , 240.21 (2) shall terminate tap from panel bus to sub panel in breaker,or fuses, 250.24(A)(5) isolate grds and nuetrals at sub panel and pump disconnect 200.7 shall ID white wire used as phase conductor, 344.46 bushings for rigid nipples. 348.30 secure flex 7/26/2002 12:40:25 PM
ELE02-01696 Permanent Service7/25/20027/26/20027/26/2002 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 07/25/2002 at 12:50:55. Contact: ###-####.

p/s u/g new ok 7/25/2002 3:33:24 PM
ELE02-02215 Electrical Rough-In7/25/20027/26/20027/26/2002 12:00:00 AMAPART
Scheduled by a contractor via Hello! on 07/25/2002 at 13:55:21. Contact: ###-####. walls ok 7/26/2002 1:06:50 PM
ELE02-02323 Permanent Service7/25/20027/26/20027/26/2002 12:00:00 AMAFAIL
CALL FIRST TO MEET MARV ###-#### set up meeting at 9:00 am waited 10 min. they did not show up, they ca;lled I told I would meet them they did not want to wait 7/26/2002 12:44:29 PM
ELE01-03617 Electrical Rough-In7/25/20027/26/20027/26/2002 12:00:00 AMPPART
Scheduled by a contractor via Hello! on 07/25/2002 at 14:48:11. Contact: ###-####. u/g for parking lot lights 7/26/2002 3:37:03 PM
ELE02-02340 Electrical Rough-In7/26/20027/26/20027/26/2002 12:00:00 AMPFAIL
r/i david ###-#### 230.28 guy kit, 250.53(D) 2 grd rods, proper space apart note even from phone grd rod, 250.64 (E) G E C continuous from point of attachment to cabinet cor. posted called 7/26/2002 4:26:09 PM
ELE02-01832 Rough-In Permanent Service7/26/20027/26/20027/26/2002 12:00:00 AMPFAIL
chris cover ; Phone #: ###-#### cor. and 45.00 reinspection fee due called 110.12 seal ko s, 310.16 shall provide proper sized branch circuit wiring to fixtures that are daisy chained, shall have all make up of wires at boxes complete before inspection is requested 7/26/2002 5:54:28 PM
ELE02-01775 Final7/26/20027/26/20027/26/2002 12:00:00 AMPPASS
###-#### karen ok 7/26/2002 6:45:24 PM
ELE02-02280 Permanent Service7/26/20027/26/20027/26/2002 12:00:00 AMPPASS
###-#### p/s u/g new ok 7/26/2002 6:25:52 PM
ELE02-02343 Rough-In Permanent Service7/26/20027/26/20027/26/2002 12:00:00 AMPPASS
PAT ###-#### ok 7/29/2002 11:35:02 AM