Inspections for the day of: Friday, July 26, 2002.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD01-00941 FIRE-Conference7/25/20027/26/20027/26/2002 12:00:00 AMADONE
spoke with the contractor about life/safety requirements prior to the final inspection 7/26/2002 11:02:09 AM
FIR02-00253 INSP-Alarm Testing7/25/20027/26/20027/26/2002 12:00:00 AMAFAIL
signals to the monitoring station are incorrect, a/v's are overspaced in classrooms, smoke detectors overspaced due to beams in corridors and rooms. I stopped the inspection. Basically inspection needs to start at the beginning. 7/26/2002 10:35:22 AM
BLD02-00820 FIRE-Final Inspection7/26/20027/26/20027/26/2002 12:00:00 AMPPASS
fire life/safety finaled 7/26/2002 1:58:06 PM
FIR02-00270 INSP-Final Inspection7/26/20027/26/20027/26/2002 12:00:00 AMPFAIL
per the review comments the fire sprinkler monitoring panel needs to meet current code. the existing panel does not. I notified the contractor by correction notice that fire alarm submittals will be required. 7/26/2002 4:05:39 PM
FIR01-00572 INSP-Final Inspection7/25/20027/26/20027/26/2002 12:00:00 AMPCANC
I spoke with shilo about the correction notice. Trent was not sure all items had been corrected and would get back to me today or monday 7/26/2002 4:13:21 PM
FIR02-00088 INSP-Final Inspection7/24/20027/26/20027/26/2002 12:00:00 AMPCANC
cancelled by contractor 7/26/2002 1:20:43 PM