Inspections for the day of: Tuesday, July 26, 2005.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-01049 Conference7/26/20057/26/20057/26/2005 3:14:09 PMPCANC
Scheduled by a contractor via Hello! on 7/26/2005 at 7:36:27 AM. Contact: ###-####. no conference they wanted a r/i, see added r/i
ELE05-02248 Rough-In Permanent Service7/26/20057/26/20057/26/2005 2:47:25 PMPPASS
brian; Phone #: ###-#### Internet Inspection Request from: Barbara Moore r/i ok p/s u/g new ok
ELE05-01920 Electrical Rough-In7/26/20057/26/20057/26/2005 2:15:47 PMPPART
Scheduled by a contractor via Hello! on 7/26/2005 at 8:40:03 AM. Contact: ###-####. u/g core hole for light fixtures ok
ELE05-02639 Final7/26/20057/26/20057/26/2005 1:20:07 PMPPASS
REINSPECTION FOR HOT TUB ONLY, PLEASE; Phone #: ###-#### Internet Inspection Request from: Barry Kendall ok
ELE05-02675 Temporary Service7/25/20057/26/20057/26/2005 12:57:05 PMAFAIL
###-#### - ROGER no sticker or address called
ELE05-02674 Temporary Service7/25/20057/26/20057/26/2005 12:56:24 PMAFAIL
###-#### - ROGER no sticker ,or address called
ELE05-02384 Permanent Service7/26/20057/26/20057/26/2005 12:32:27 PMPPASS
CONTACT: ALEX KELLY; Phone #: ###-#### Internet Inspection Request from: Deb McCoy p/s u/g new meter womens fitness ok
ELE05-02292 Permanent Service7/26/20057/26/20057/26/2005 12:31:42 PMPPASS
CONTACT: ALEX KELLY; Phone #: ###-#### Internet Inspection Request from: Deb McCoy p/s u/g new meter H&R Block ok
ELE05-02657 Temporary Service7/25/20057/26/20057/26/2005 10:15:35 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack 2nd cor. posted called 200.6 shall not use white for bonding
ELE05-02586 Electrical Rough-In7/25/20057/26/20057/26/2005 9:37:39 AMAPART
Scheduled by a contractor via Hello! on 7/25/2005 at 3:24:32 PM. Contact: ###-####. lab walls ok
ELE05-01566 Electrical Rough-In7/25/20057/26/20057/26/2005 9:19:39 AMAFAIL
Ceiling grid inspection. If not open, lock box is on door to the left of the front door. Key pad 1931.; Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot cor. posted called 110.26(F)(1) correction not made needs to remove sprinkler line from above sub panel 1st floor and new violation clearence above panel 2nd floor, remove drain vent and duct or install hard structural ceiling per conversation on 05-15-05
ELE05-02681 Electrical Rough-In7/25/20057/26/20057/26/2005 8:06:53 AMAPART
lynn ###-#### walls and hard ceiling new drive up window
ELE05-01363 DOC - Permit Finaled7/26/20057/26/20057/26/2005 12:00:00 AMAPASS
ELE05-01566 Electrical Rough-In7/26/20057/26/20057/26/2005 12:00:00 AMAPART
Ceiling grid inspection. If not open, lock box is on door to the left of the front door. Key pad 1931.; Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot ceiling ok for 1st floor only
ELE05-01049 Electrical Rough-In7/26/20057/26/20057/26/2005 12:00:00 AMPFAIL
cor. posted met owner 314.17&110.3 replace cutin boxes broken clamps, and sheath shall extent 1/4" into box, 300.4 11/4" and nail plates, 300.14 6" free length, 314,16 box fill