Inspections for the day of: Tuesday, July 26, 2005.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-00669 Final7/26/20057/26/20057/26/2005 4:42:48 PMPFAIL
leon; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr, left corr notice on panel, 352.30(A) rnc shall be strapped within 3' of box, 210.8(A)(7) gfci shall be provided within 6' of laundry sink, 314.21 drywall shall be repaired, 313.23(A)(1) there shall be no screws in boxes, 314.25 boxes shall have covers, 314.17(C) nm cable shall be stapled within 8" of box, 406.5 cover plates shall seat against mounting surface, 430.107 jetted tub shall have access, BCC disposal shall be installed for final
ELE05-00765 Final7/26/20057/26/20057/26/2005 4:36:05 PMPPASS
Scheduled by a contractor via Hello! on 7/26/2005 at 8:26:24 AM. Contact: ###-####. called contr about gfci in dining room, ok to final
ELE05-02626 Final7/26/20057/26/20057/26/2005 4:34:42 PMPNR
kevin or alex; Phone #: ###-#### Internet Inspection Request from: Barbara Moore called contr, too many items for them to review before service or final. they will recall. Items too look for are: Baldor motor and system not listed, 1 ground rod, connector on w/p box not water-tight, job id sticker not posted, panel with drive unit not listed, overcurrent protection to and or from drive not provided, drive panel does not have clear work space, fencing will not leave work space for service panel, 3/4" emt connectors not ul listed as raintight
ELE05-02062 Final7/26/20057/26/20057/26/2005 2:14:48 PMPPASS
Scheduled by a contractor via Hello! on 7/26/2005 at 9:50:24 AM. Contact: ###-####. ok to final
ELE05-02662 Rough-In Permanent Service7/25/20057/26/20057/26/2005 2:13:50 PMPPASS
clyde ###-#### ric ok, p/s u/g n ok
ELE05-01565 Final7/26/20057/26/20057/26/2005 2:13:15 PMPPASS
Scheduled by a contractor via Hello! on 7/26/2005 at 8:31:29 AM. Contact: ###-####. ok to final
ELE05-02483 Permanent Service7/26/20057/26/20057/26/2005 12:54:28 PMPFAIL
Please call Chris when you are on your way to inspect. ###-#### THANK YOU; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH label is for bkr panel only. Talked to elect to resolve listing for ass'y.
ELE05-02661 Rough-In Permanent Service7/25/20057/26/20057/26/2005 9:52:50 AMAPASS
clyde ###-#### ric ok, p/s u/g n ok
ELE05-02671 Permanent Service7/25/20057/26/20057/26/2005 9:34:34 AMAPASS
Call Joe at ###-#### for entrance Internet Inspection Request from: Joseph Zumwalt corr made, p/s u/g exst ok
ELE05-02585 Electrical Rough-In7/25/20057/26/20057/26/2005 8:39:01 AMAPASS
Scheduled by a contractor via Hello! on 7/25/2005 at 11:59:01 AM. Contact: ###-####. corr made, ric ok
ELE05-02593 Temporary Service7/26/20057/26/20057/26/2005 8:24:31 AMAPASS
Temp pole off McMillan between Cloverdal and Eagle Rd at 5350 N. Brook Mist Pl in Brookdale Meadows.; Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot corr made, t/s u/g n ok
ELE05-02634 Electrical Rough-In7/25/20057/26/20057/26/2005 7:59:13 AMAPASS
ryan - Note: lightpole bases; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to pour pole bases only. Need to see u/g to bases from source of power.
ELE05-02295 Temporary Service7/26/20057/26/20057/26/2005 12:00:00 AMPPASS
corr made, t/s u/g n ok