MIS05-00070
| MIS-Aging Inspection | 7/25/2005 | 7/26/2005 | 7/28/2005 9:12:21 AM | A | FAIL |
|
|
Provide sign at main entry/exit stating "this door to remain unlocked while building is occupied", provide lever hardware and remove thumbturn at door from garage area on the south side, provide lever hardware at restroom door. Tyson is the contact at ###-####.
|
FIR05-00401
| INSP-Sprinkler Rough-in/Hydro | 7/26/2005 | 7/26/2005 | 7/26/2005 4:29:01 PM | P | FAIL |
|
|
Pendent heads along storefront canopy do not meet OH2 spacing requirements dictated by this occupant type and use for this specific area (see review notes- re-submittals req. for any changes), EQ attatchments in wood truss members must be through bolted, attic heads along sloped ceilings must orient deflector with the slope, perform hydrostatic test when system is complete and changes have been made.
|
FIR05-00372
| INSP-Sprinkler Rough-in | 7/25/2005 | 7/26/2005 | 7/26/2005 4:14:21 PM | P | PART |
|
|
2nd floor projection room and mezzanine, theatres #8 and #9 are good for cover. Final head location will be examined after ceiling grid is installed. Approved rough-in areas are initialed on stamped plan set.
|
FIR05-00414
| INSP-Final Inspection | 7/26/2005 | 7/26/2005 | 7/26/2005 1:54:35 PM | P | PART |
|
|
Fire sprinkler rough-in is satisfactory, will final permit after walls are built for verification of spacing requirements affecting relocated heads.
|
MIS05-00002
| FIR-Final | 7/25/2005 | 7/26/2005 | 7/26/2005 10:28:04 AM | A | PASS |
|
|
Life safety passed inspection.
|
FIR04-00593
| INSP-Final Inspection | 7/25/2005 | 7/26/2005 | 7/26/2005 9:52:55 AM | A | PART |
|
|
One escutcheon is missing on a dry pendent at front porch, tape needs to be removed from escutcheons on heads at east side of porch.
|
FIR05-00294
| INSP-Final Inspection | 7/26/2005 | 7/26/2005 | 7/26/2005 12:00:00 AM | A | PASS |
|
|
Fire alarm finaled.
|
BLD04-02988
| FIRE-Final Inspection | 7/26/2005 | 7/26/2005 | 7/26/2005 12:00:00 AM | A | PASS |
|
|
Fire life safety finaled.
|
FIR05-00206
| INSP-Final Inspection | 7/26/2005 | 7/26/2005 | 7/26/2005 12:00:00 AM | A | PASS |
|
|
Underground permit finaled.
|