Inspections for the day of: Wednesday, July 26, 2006.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-01203 Final7/21/20067/26/20067/26/2006 3:59:03 PMPPASS
need final on new building. thank you.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH corr made, ok to final, signed card
ELE06-02239 Final7/26/20067/26/20067/26/2006 3:26:00 PMPFAIL
met elect, left corr notice, 358.26 there shall not be over 360 degree bends between pullpoints, example between conduit bodies and boxes
ELE06-02741 Electrical Rough-In7/25/20067/26/20067/26/2006 3:20:18 PMPPASS
john (cell#) - call for access; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok to cover u/g for equipotential plane and conduits
ELE06-02090 Final7/26/20067/26/20067/26/2006 2:38:34 PMPPASS
shawn; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr made, ok to final
ELE06-02633 Conference7/25/20067/26/20067/26/2006 1:52:40 PMPDONE
General contractor would like to conference about the classification. Please call with a meeting time.; Phone #: ###-#### Internet Inspection Request from: Celinda Winters met contr and elect to discuss a letter stating purpose of garage
ELE06-02704 Rough-In Permanent Service7/25/20067/26/20067/26/2006 12:23:46 PMAPART
jim - Note: underground pipe; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to cover 100' more u/g, same trench
ELE06-02750 Rough-In Permanent Service7/25/20067/26/20067/26/2006 9:32:21 AMAPASS
joe; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called contr, left survey, nec 314.20 in walls of combustible material, boxes shall be flush with the finished surface, 210.52(C)(1) recpts shall be within 2' of edge of sink in kitchen, ric ok, p/s u/g n ok
ELE06-02742 Electrical Rough-In7/25/20067/26/20067/26/2006 8:56:52 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: Sean DeLacy called, left corr notice, nec 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, BCC all make-up shall be done (foyer box), power riser shall be installed
ELE06-02230 Final7/25/20067/26/20067/26/2006 8:24:48 AMAPASS
Scheduled by a contractor via Hello! on 7/25/2006 at 4:35:29 PM. Contact: ###-####. ok to final