Inspections for the day of: Thursday, July 26, 2007.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-02409 Electrical Rough-In7/25/20077/26/20077/26/2007 3:54:57 PMPPASS
Electrician is Steve Johnson Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer 1 wall ok to cover, told contr to change address and to add to or get other permit for server area
ELE06-00105 Final7/24/20077/26/20077/26/2007 3:35:41 PMPPASS
Final - pls call Jim w/Doherty @ ###-#### 30min prior so that he can meet the inspector to walk through - Jim will be 2 houses down from there. Scheduled by Heather w/Doherty Phone #: ###-#### Internet Inspection Request from: Heather Packer met contr, ok to final
ELE07-02589 Electrical Rough-In7/24/20077/26/20077/26/2007 2:54:46 PMPPASS
RI - for questions pls call Jim w/Doherty @ ###-####. Scheduled by Heather w/Doherty Phone #: ###-#### Internet Inspection Request from: Heather Packer ric kitchen and entry ok
ELE07-02589 Permanent Service7/24/20077/26/20077/26/2007 2:20:42 PMPPASS
service - questions pls call Jim w/Doherty @ ###-####. Scheduled by Heather w/Doherty Phone #: ###-#### Internet Inspection Request from: Heather Packer p/s o/h rec ok
ELE07-01719 Final7/26/20077/26/20077/26/2007 2:03:20 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Brandon Blackham ok to final
ELE07-01423 Final7/26/20077/26/20077/26/2007 1:20:46 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Brandon Blackham ok to final
ELE07-02501 Permanent Service7/26/20077/26/20077/26/2007 12:29:57 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Dan Surerus p/s exst meter pak n ok (2 meters)
ELE07-00780 Permanent Service7/25/20077/26/20077/26/2007 11:07:19 AMAPASS
randy Phone #: ###-#### corrections made, p/s u/g n ok
ELE07-02522 Permanent Service7/25/20077/26/20077/26/2007 10:39:26 AMACANC
joseph; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang see failed inspection
ELE07-02522 Final7/25/20077/26/20077/26/2007 10:05:54 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer called, left corr notice, BCC job id sticker shall be posted, 312.5 all conductors entering enclosures shall be provided with abrasion protection, 350.30 lfmc shall be supported within 12" of box, 408.4 shall provide circuit directory
ELE07-02579 Electrical Rough-In7/25/20077/26/20077/26/2007 9:40:26 AMAPASS
reinspection UG cover Phone #: ###-#### Internet Inspection Request from: Jari Rivers corrections made, pool equip u/g only ok to cover, need to see equipotential plane ltr
ELE07-02501 Permanent Service7/25/20077/26/20077/26/2007 9:26:59 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: Dan Surerus called contr, left corr notice, nec 110.26(F)(1)(b) shall provide protection to avoid damage to elect equip from condensation, leaks or breaks over panel F, BCC addressing shall be correct and posted
ELE07-02451 Electrical Rough-In7/25/20077/26/20077/26/2007 8:50:45 AMAPART
Under Ground Inspect. Rick Sendra Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson ok to pour from xfmr to service gear
ELE07-01423 Final7/25/20077/26/20077/26/2007 8:09:22 AMANH
Phone #: ###-#### Internet Inspection Request from: Brandon Blackham called, left card, told to recall, doors locked
ELE07-01719 Final7/25/20077/26/20077/26/2007 8:07:17 AMANR
Phone #: ###-#### Internet Inspection Request from: Brandon Blackham garage locked, reverse polarity, need permanent nameplates for meters, called contr, told to recall