ELE07-02409
| Electrical Rough-In | 7/25/2007 | 7/26/2007 | 7/26/2007 3:54:57 PM | P | PASS |
|
|
Electrician is Steve Johnson Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer 1 wall ok to cover, told contr to change address and to add to or get other permit for server area
|
ELE06-00105
| Final | 7/24/2007 | 7/26/2007 | 7/26/2007 3:35:41 PM | P | PASS |
|
|
Final - pls call Jim w/Doherty @ ###-#### 30min prior so that he can meet the inspector to walk through - Jim will be 2 houses down from there. Scheduled by Heather w/Doherty Phone #: ###-#### Internet Inspection Request from: Heather Packer met contr, ok to final
|
ELE07-02589
| Electrical Rough-In | 7/24/2007 | 7/26/2007 | 7/26/2007 2:54:46 PM | P | PASS |
|
|
RI - for questions pls call Jim w/Doherty @ ###-####. Scheduled by Heather w/Doherty Phone #: ###-#### Internet Inspection Request from: Heather Packer ric kitchen and entry ok
|
ELE07-02589
| Permanent Service | 7/24/2007 | 7/26/2007 | 7/26/2007 2:20:42 PM | P | PASS |
|
|
service - questions pls call Jim w/Doherty @ ###-####. Scheduled by Heather w/Doherty Phone #: ###-#### Internet Inspection Request from: Heather Packer p/s o/h rec ok
|
ELE07-01719
| Final | 7/26/2007 | 7/26/2007 | 7/26/2007 2:03:20 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Brandon Blackham ok to final
|
ELE07-01423
| Final | 7/26/2007 | 7/26/2007 | 7/26/2007 1:20:46 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Brandon Blackham ok to final
|
ELE07-02501
| Permanent Service | 7/26/2007 | 7/26/2007 | 7/26/2007 12:29:57 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Dan Surerus p/s exst meter pak n ok (2 meters)
|
ELE07-00780
| Permanent Service | 7/25/2007 | 7/26/2007 | 7/26/2007 11:07:19 AM | A | PASS |
|
|
randy Phone #: ###-#### corrections made, p/s u/g n ok
|
ELE07-02522
| Permanent Service | 7/25/2007 | 7/26/2007 | 7/26/2007 10:39:26 AM | A | CANC |
|
|
joseph; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang see failed inspection
|
ELE07-02522
| Final | 7/25/2007 | 7/26/2007 | 7/26/2007 10:05:54 AM | A | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer called, left corr notice, BCC job id sticker shall be posted, 312.5 all conductors entering enclosures shall be provided with abrasion protection, 350.30 lfmc shall be supported within 12" of box, 408.4 shall provide circuit directory
|
ELE07-02579
| Electrical Rough-In | 7/25/2007 | 7/26/2007 | 7/26/2007 9:40:26 AM | A | PASS |
|
|
reinspection UG cover Phone #: ###-#### Internet Inspection Request from: Jari Rivers corrections made, pool equip u/g only ok to cover, need to see equipotential plane ltr
|
ELE07-02501
| Permanent Service | 7/25/2007 | 7/26/2007 | 7/26/2007 9:26:59 AM | A | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Dan Surerus called contr, left corr notice, nec 110.26(F)(1)(b) shall provide protection to avoid damage to elect equip from condensation, leaks or breaks over panel F, BCC addressing shall be correct and posted
|
ELE07-02451
| Electrical Rough-In | 7/25/2007 | 7/26/2007 | 7/26/2007 8:50:45 AM | A | PART |
|
|
Under Ground Inspect. Rick Sendra Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson ok to pour from xfmr to service gear
|
ELE07-01423
| Final | 7/25/2007 | 7/26/2007 | 7/26/2007 8:09:22 AM | A | NH |
|
|
Phone #: ###-#### Internet Inspection Request from: Brandon Blackham called, left card, told to recall, doors locked
|
ELE07-01719
| Final | 7/25/2007 | 7/26/2007 | 7/26/2007 8:07:17 AM | A | NR |
|
|
Phone #: ###-#### Internet Inspection Request from: Brandon Blackham garage locked, reverse polarity, need permanent nameplates for meters, called contr, told to recall
|