Inspections for the day of: Thursday, July 26, 2007.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD06-01535 FIRE-Final Inspection7/26/20077/26/20077/27/2007 1:43:00 PMPPASS
Fire life safety inspection passed.
FIR07-00573 INSP-Final Inspection7/25/20077/26/20077/26/2007 5:13:19 PMAPASS
Hood suppression systems operated correctly under test conditions, noted missing K class PFE's and signage designating manual pulls to be installed prior to final and verified by K. Sandahl.
FIR07-00392 INSP-Final Inspection7/25/20077/26/20077/26/2007 4:32:45 PMPFAIL
Two SD did not function upon testing, interconnection for the access control egress mag locks are not complete. AV notification and two manual pull stations tested satisfactory.
FIR07-00540 INSP-Final Inspection7/26/20077/26/20077/26/2007 3:37:28 PMPCANC
No time available to complete this inspection.
FIR06-00959 INSP-Final Inspection7/24/20077/26/20077/26/2007 3:30:53 PMAPART
Fire sprinkler install is approved for sheets FP 2.0.1,2.1.1,2.1.4, one head is blocked by ductwork & one hallway head is missing an escutcheon-see sheet FP 2.2.1 for locations, corrections required for sheet FP2.1.1 are satisfactory, remainder of work indicated on sheets FP2.3.1,2.2.4,2.2.2,2.2.3 is not yet completed.
FIR07-00249 INSP-Final Inspection7/25/20077/26/20077/26/2007 2:20:25 PMAPASS
Fire sprinkler demo permit work finaled.
FIR07-00563 INSP-Final Inspection7/26/20077/26/20077/26/2007 1:13:38 PMPCANC
No time available to complete this inspection.
FIR07-00275 INSP-Final Inspection7/25/20077/26/20077/26/2007 1:09:40 PMACANC
No time available to complete this inspection.
FIR07-00554 INSP-Final Inspection7/25/20077/26/20077/26/2007 12:58:13 PMAPART
Two heads as marked on approved plans exceed spacing limitations, see plans for areas annotated okay for ceiling cover.
FIR07-00275 INSP-Alarm Testing7/25/20077/26/20077/26/2007 12:33:23 PMACANC
Duplicate inspection request.
FIR07-00280 INSP-Final Inspection7/25/20077/26/20077/26/2007 12:22:54 PMAPASS
Required corrections verified for compliance, fire sprinkler permit finaled.
BLD07-01475 FIRE-Final Inspection7/25/20077/26/20077/26/2007 12:20:45 PMAPASS
Fire life safety is acceptable pending repair of one "sticking" door leaf at the east exit pair of doors, existing service doors at the 1st floor kitchen area to be replaced during building upgrade in process per tenant and general contractor.
FIR07-00557 INSP-Final Inspection7/25/20077/26/20077/26/2007 12:16:22 PMAPASS
Fire sprinkler final inspection passed, permit finaled.
FIR06-00704 INSP-Final Inspection7/25/20077/26/20077/26/2007 11:55:35 AMAFAIL
Lacking notification coverage at the basement restrooms, low air switch is not adjusted properly, identify zone descriptors with central station, missing covers at two control modules, provide lock and label at the breaker to the FACP, provide as-built plans correctly reflecting field mods including deleted monitor points, need map at the panel, 2nd and 3rd floor ID's and elevator not tested at this time, SD at the 2nd floor lobby to be relocated to the drop ceiling.
FIR06-00728 INSP-Final Inspection7/25/20077/26/20077/26/2007 11:47:07 AMAFAIL
Low air switch at the dry system riser is not set properly, air compressor must be hard wired without an off switch, lacking coverage at one storage room in the basement, provide 911 signage at the outside bell, covered heads and missing escutcheons at some locations, head in the riser room is covered with fireproofing, inspection concluded at this time due to number of defficiencies.
BLD06-00688 FIRE-Final Inspection7/25/20077/26/20077/26/2007 11:42:38 AMANR
Need project related fire alarm and fire sprinkler permits finaled before life safety final inspection and approval.
FIR07-00039 FIR-Aging Inspection7/26/20077/26/20077/26/2007 8:09:34 AM DEFR
wip
BLD07-00842 FIRE-Final Inspection7/25/20077/26/20077/26/2007 12:00:00 AMADONE
justin; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang