BLD06-01535
| FIRE-Final Inspection | 7/26/2007 | 7/26/2007 | 7/27/2007 1:43:00 PM | P | PASS |
|
|
Fire life safety inspection passed.
|
FIR07-00573
| INSP-Final Inspection | 7/25/2007 | 7/26/2007 | 7/26/2007 5:13:19 PM | A | PASS |
|
|
Hood suppression systems operated correctly under test conditions, noted missing K class PFE's and signage designating manual pulls to be installed prior to final and verified by K. Sandahl.
|
FIR07-00392
| INSP-Final Inspection | 7/25/2007 | 7/26/2007 | 7/26/2007 4:32:45 PM | P | FAIL |
|
|
Two SD did not function upon testing, interconnection for the access control egress mag locks are not complete. AV notification and two manual pull stations tested satisfactory.
|
FIR07-00540
| INSP-Final Inspection | 7/26/2007 | 7/26/2007 | 7/26/2007 3:37:28 PM | P | CANC |
|
|
No time available to complete this inspection.
|
FIR06-00959
| INSP-Final Inspection | 7/24/2007 | 7/26/2007 | 7/26/2007 3:30:53 PM | A | PART |
|
|
Fire sprinkler install is approved for sheets FP 2.0.1,2.1.1,2.1.4, one head is blocked by ductwork & one hallway head is missing an escutcheon-see sheet FP 2.2.1 for locations, corrections required for sheet FP2.1.1 are satisfactory, remainder of work indicated on sheets FP2.3.1,2.2.4,2.2.2,2.2.3 is not yet completed.
|
FIR07-00249
| INSP-Final Inspection | 7/25/2007 | 7/26/2007 | 7/26/2007 2:20:25 PM | A | PASS |
|
|
Fire sprinkler demo permit work finaled.
|
FIR07-00563
| INSP-Final Inspection | 7/26/2007 | 7/26/2007 | 7/26/2007 1:13:38 PM | P | CANC |
|
|
No time available to complete this inspection.
|
FIR07-00275
| INSP-Final Inspection | 7/25/2007 | 7/26/2007 | 7/26/2007 1:09:40 PM | A | CANC |
|
|
No time available to complete this inspection.
|
FIR07-00554
| INSP-Final Inspection | 7/25/2007 | 7/26/2007 | 7/26/2007 12:58:13 PM | A | PART |
|
|
Two heads as marked on approved plans exceed spacing limitations, see plans for areas annotated okay for ceiling cover.
|
FIR07-00275
| INSP-Alarm Testing | 7/25/2007 | 7/26/2007 | 7/26/2007 12:33:23 PM | A | CANC |
|
|
Duplicate inspection request.
|
FIR07-00280
| INSP-Final Inspection | 7/25/2007 | 7/26/2007 | 7/26/2007 12:22:54 PM | A | PASS |
|
|
Required corrections verified for compliance, fire sprinkler permit finaled.
|
BLD07-01475
| FIRE-Final Inspection | 7/25/2007 | 7/26/2007 | 7/26/2007 12:20:45 PM | A | PASS |
|
|
Fire life safety is acceptable pending repair of one "sticking" door leaf at the east exit pair of doors, existing service doors at the 1st floor kitchen area to be replaced during building upgrade in process per tenant and general contractor.
|
FIR07-00557
| INSP-Final Inspection | 7/25/2007 | 7/26/2007 | 7/26/2007 12:16:22 PM | A | PASS |
|
|
Fire sprinkler final inspection passed, permit finaled.
|
FIR06-00704
| INSP-Final Inspection | 7/25/2007 | 7/26/2007 | 7/26/2007 11:55:35 AM | A | FAIL |
|
|
Lacking notification coverage at the basement restrooms, low air switch is not adjusted properly, identify zone descriptors with central station, missing covers at two control modules, provide lock and label at the breaker to the FACP, provide as-built plans correctly reflecting field mods including deleted monitor points, need map at the panel, 2nd and 3rd floor ID's and elevator not tested at this time, SD at the 2nd floor lobby to be relocated to the drop ceiling.
|
FIR06-00728
| INSP-Final Inspection | 7/25/2007 | 7/26/2007 | 7/26/2007 11:47:07 AM | A | FAIL |
|
|
Low air switch at the dry system riser is not set properly, air compressor must be hard wired without an off switch, lacking coverage at one storage room in the basement, provide 911 signage at the outside bell, covered heads and missing escutcheons at some locations, head in the riser room is covered with fireproofing, inspection concluded at this time due to number of defficiencies.
|
BLD06-00688
| FIRE-Final Inspection | 7/25/2007 | 7/26/2007 | 7/26/2007 11:42:38 AM | A | NR |
|
|
Need project related fire alarm and fire sprinkler permits finaled before life safety final inspection and approval.
|
FIR07-00039
| FIR-Aging Inspection | 7/26/2007 | 7/26/2007 | 7/26/2007 8:09:34 AM | | DEFR |
|
|
wip
|
BLD07-00842
| FIRE-Final Inspection | 7/25/2007 | 7/26/2007 | 7/26/2007 12:00:00 AM | A | DONE |
|
|
justin; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang
|