Inspections for the day of: Monday, July 26, 2010.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD09-02300 BLD-Aging Inspection7/26/20107/26/20107/26/2010 3:22:31 PMPNR
Per Bill revised drawings are being submitted and the inspection will hopefully be called in next week.
BLD10-01505 FIRE-Final Inspection7/26/20107/26/20107/26/2010 3:19:55 PMPPASS
Life safety passed.
FIR10-00352 INSP-Final Inspection7/26/20107/26/20107/26/2010 3:19:28 PMPPASS
Permit finaled
BLD09-02032 FIRE-Final Inspection7/23/20107/26/20107/26/2010 2:48:48 PMAFAIL
Upon review of the city approved plans there are two duct smoke detectors shown on the Mechanical sheets and they are installed as well. These two detectors will be required to be tested with the required remote annunciators or have engineer approval to delete since the drawings show the units at only 1700 cfm. All other items are ok.
BLD10-01444 FIRE-Final Inspection7/26/20107/26/20107/26/2010 1:57:29 PMPCANC
Wrong permit called in.
BLD10-01375 FIRE-Final Inspection7/26/20107/26/20107/26/2010 1:18:21 PMPPASS
Life safety passed.
FIR10-00354 INSP-Final Inspection7/23/20107/26/20107/26/2010 11:31:54 AMAPASS
Permit finaled
FIR09-00707 INSP-Final Inspection7/22/20107/26/20107/26/2010 11:08:37 AMAPASS
The forward flush passed. Permit for Phase I passed.