Inspections for the day of: Tuesday, July 26, 2011.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00285 INSP-Sprinkler Rough-in7/25/20117/26/20117/26/2011 3:27:07 PMPPASS
Underground piping is ok to cover 60' from the first 22 degree fitting towards the building.
FIR11-00345 INSP-Sprinkler Rough-in7/25/20117/26/20117/26/2011 3:18:10 PMAFAIL
The rough-in itself appears ok but extensive pipe routing changes have been made. Plan modifications are required. Per Tim Frost the sidewall head show at the garage door to the residence can be changed to a pendant. I verified that the pendant heads will provide coverage under the soffits in the living room and in the entry ways to the two bedrooms in the lower level. No tenting has been done yet. I let Don know that a approval for cover would not be given until the plans are re-approved and the tenting was approved. Also the backflow preventor installed is not the one that was submitted on. No underground piping from the street to the bottom of the backflow was inspected or even present.
FIR11-00285 INSP-Sprinkler Rough-in7/25/20117/26/20117/26/2011 3:11:43 PMAPASS
Underground is ok to cover up to the 22 degree fitting
BLD11-00788 FIRE-Final Inspection7/26/20117/26/20117/26/2011 2:30:43 PMAPART
Partial final for the Phase I portion of the TI. See the city approved plans for three new offices, storage room and HIPA storage room where life safety is passed. Near the three new offices there are two overspaced sprinklers and fire alarm audio/visual modifications that are needed.
FIR11-00247 INSP-Sprinkler Rough-in/Hydro7/25/20117/26/20117/26/2011 12:57:47 PMAPASS
Underground hydro passed
FIR11-00289 INSP-Sprinkler Rough-in7/25/20117/26/20117/26/2011 12:41:01 PMAPASS
Need to have as-builts and provide coverage beneath the audio/visual booth. All other work is complete.
BLD08-00227 FIRE-Final Inspection7/25/20117/26/20117/26/2011 10:53:12 AMAPASS
life safety passed
BLD11-01619 FIRE-Final Inspection7/25/20117/26/20117/26/2011 9:14:54 AMAPASS
life safety passed