Inspections for the day of: Tuesday, July 26, 2016.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD14-03207 FIRE-Conference7/26/20167/26/20167/26/2016 2:03:38 PMPCANC
Fire conference rescheduled for 27JULY2016
FIR16-00010 INSP-Final Inspection7/25/20167/26/20167/26/2016 1:46:19 PMAPASS
Final fire sprinkler inspection for level 8 passed/complete
FIR16-00204 INSP-Final Inspection7/25/20167/26/20167/26/2016 1:43:31 PMACANC
Inspection request for preation system rescheduled
FIR15-00861 INSP-Final Inspection7/25/20167/26/20167/26/2016 1:40:27 PMAPASS
Final fire sprinkler inspection for this permit on level 7 passed/complete
FIR15-00831 INSP-Final Inspection7/25/20167/26/20167/26/2016 1:36:22 PMAPASS
Final fire sprinkler inspection for level 6 passed/complete
FIR16-00057 INSP-Final Inspection7/25/20167/26/20167/26/2016 1:33:17 PMAPART
Final fire sprinkler inspection for level 2 passed/complete
FIR16-00114 INSP-Final Inspection7/25/20167/26/20167/26/2016 1:27:48 PMAPART
Fire sprinkler inspection complete for level 1
FIR15-00453 INSP-Final Inspection7/25/20167/26/20167/26/2016 1:23:41 PMAPASS
Final fire sprinkler inspection complete for core and shell
FIR16-00485 INSP-Final Inspection7/26/20167/26/20167/26/2016 1:19:13 PMPPASS
Final fire alarm inspection passed/complete
FIR16-00266 INSP-Sprinkler Rough-in7/25/20167/26/20167/26/2016 10:48:22 AMAFAIL
Tenting insulation for overhead fire sprinkler piping located in attic spaces not installed, only plastic sheeting installed, noted in fire sprinkler review notes under general requirements, section 10: "A minimum of R38 of insulation is required on top of the piping per the IEC." Overhead fire sprinkler piping located in attic spaces not approved for cover.
FIR16-00040 INSP-Sprinkler Rough-in/Hydro7/25/20167/26/20167/26/2016 10:14:03 AMAPART
Partial rough to cover inspection complete for underground supply located on the east side of building. Underground supply installed to the northeast corner of building approved for cover.
BLD16-01718 FIRE-Final Inspection7/25/20167/26/20167/26/2016 9:54:21 AMAPASS
No fire sprinkler modifications, no fire alarm modifications, fire extinguishers are in common area's with current inspection tags. Final life fire safety inspection passed/complete.
BLD16-00632 FIRE-Final Inspection7/25/20167/26/20167/26/2016 9:44:14 AMAPASS
Fire sprinkler inspection complete, no fire alarm modifications, fire extingiusher is in place with current inspection tag. Final life fire safety inspection passed/complete.
FIR16-00234 INSP-Final Inspection7/22/20167/26/20167/26/2016 9:35:43 AMAPASS
Final fire sprinkler inspection passed/complete
BLD13-00223 FIRE-Final Inspection7/25/20167/26/20167/26/2016 8:44:08 AMAPASS
No fire sprinklers, no fire alarm modifications, fire extinguishers are in place with current inspection tags. Final life fire safety inspection passed/complete.
FIR16-00329 INSP-Final Inspection7/25/20167/26/20167/26/2016 5:48:01 AMAPASS
Final fire alarm inspection passed/complete
FIR16-00294 INSP-Final Inspection7/25/20167/26/20167/26/2016 5:41:52 AMAPASS
Final fire alarm inspection passed/complete
FIR16-00272 INSP-Final Inspection7/25/20167/26/20167/26/2016 5:39:46 AMAPASS
Final fire alarm inspection passed/complete