ELE19-01817
| Final | 7/26/2019 | 7/26/2019 | 7/26/2019 2:10:43 PM | P | FAIL |
|
|
garage code 1957e Phone #: ###-#### Inspection requested via web by Alan Lusk Garage GFCI dead. W/P receps dead. 14-2 Stubbed out E side of house shall terminate in box.
|
ELE19-02239
| Final | 7/26/2019 | 7/26/2019 | 7/26/2019 1:18:14 PM | P | PASS |
|
|
MITCH Phone #: ###-#### Final ok
|
ELE19-01060
| Final | 7/26/2019 | 7/26/2019 | 7/26/2019 12:50:46 PM | P | PASS |
|
|
GARAGE CODE 4224 Phone #: ###-#### Inspection requested via web by Bob Glenn Stack switches on back patio came with heater as a listed assembly. Final ok
|
ELE19-01920
| Electrical Rough-In | 7/25/2019 | 7/26/2019 | 7/26/2019 11:42:54 AM | A | FAIL |
|
|
Contact: Jasper McGrew.... ceiling inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden 314.25 Boxes shall have covers. (Above door in showroom.) Address is incorrect. Re-call when changed and attached to correct BLD
|
ELE19-01948
| Electrical Rough-In | 7/26/2019 | 7/26/2019 | 7/26/2019 10:53:46 AM | A | PASS |
|
|
Bathroom area walls Phone #: ###-#### Inspection requested via web by Jason Parke Bathroom and New electrical room walls only ok to cover
|
ELE19-00910
| Electrical Rough-In | 7/25/2019 | 7/26/2019 | 7/26/2019 10:40:43 AM | A | PASS |
|
|
Basement electrical rooms normal power and emergency power panels and transformer. 1st floor electrical room panels and transformers. Phone #: ###-#### Inspection requested via web by Tom Betty Main Electrical room and Basement power panels ok.
|
ELE19-02745
| Final | 7/24/2019 | 7/26/2019 | 7/26/2019 9:56:02 AM | A | FAIL |
|
|
Please inspect connection of mini split A/C Phone #: ###-#### Inspection requested via web by Kendra Lanham 440.21C Protective device shall not exceed manufacturer's values. ( was unable to gain access to house to see panel. Spoke to electrician, Said he installed 20A breaker. Nameplate is 15A max) Re-call after breaker is replaced and schedule with owner
|