Inspections for the day of: Monday, July 27, 1998.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorCarl Dependahl
TitleBLD-COM/RES INSPECTOR
Phone #794-9492
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD98-01708 INSP - Framing/Rough-in7/27/19987/27/19987/27/1998 12:00:00 AMANR
conf w/ cont; need replace let-ins cut w/ plywood or equiv.
BLD98-01815 INSP - Framing/Rough-in7/27/19987/27/19987/27/1998 12:00:00 AMPNR
conf w/ bldr re exits...told to install ADA hdwe at doors, remove dead bolts, etc.
BLD97-00074 INSP - Final7/27/19987/27/19987/27/1998 12:00:00 AMPFAIL
JERRY ###-####...need pub wks, htg, etc.
BLD97-03582 INSP - Framing/Rough-in7/27/19987/27/19987/27/1998 12:00:00 AMPNR
no insp; conf w/ bldr re use of foam plastic insul in roof ass'y...gave rules for use from UBC 2602 re listing, smoke flame etc.
BLD98-00271 INSP - Framing/Rough-in7/27/19987/27/19987/27/1998 12:00:00 AMPFAIL
still need truss repair, etc
BLD98-00686 INSP - Foundation7/27/19987/27/19987/27/1998 12:00:00 AMPPART
foundation wall/ ###-#### pahds onsite ok to install, looks ok.
BLD98-00758 INSP - Framing/Rough-in7/27/19987/27/19987/27/1998 12:00:00 AMPFAIL
C/N. NEED VERIFY TRUSS BRACING FIX, COMPLETE FIREBLOCKING AT WALL PENETRATIONS ABOVE CLG. STILL NEED SURVEY REPORT.
BLD98-00758 INSP - Energy code compliance7/27/19987/27/19987/27/1998 12:00:00 AMPFAIL
INSULATION JOE ###-####
BLD98-01371 INSP - Energy code compliance7/27/19987/27/19987/27/1998 12:00:00 AMPPART
INS OK
BLD98-01371 INSP - Framing/Rough-in7/27/19987/27/19987/27/1998 12:00:00 AMPPART
TJI FIX OK OVER GARAGE
BLD98-01536 INSP-Conference7/27/19987/27/19987/27/1998 12:00:00 AMPPASS
would like you to call him wade ###-####/has questions that may be resolved over phone. OK TO USE FURR DOWN TO RUN WIRE; NEED TO GET W/ WES RE " VARIANCE ".