BLD03-02891
| FIRE-Final Inspection | 7/26/2004 | 7/27/2004 | 7/27/2004 12:00:00 AM | A | FAIL |
|
|
Inspection was for multiple rooms in the next phase of the project. See city approved plans, sheets A2.2, A2.3 and A2.5 for the specific rooms and deficiencies. There are card readers and door magnets being installed. I contacted Nick with Synergy and Jason with AEI about IFC and IBC requirements for access controlled egress doors. These items are not shown on the approved fire alarm plans. Plans will require possible resubmittals. 7/27/2004 10:27:32 AM
|
FIR04-00384
| INSP-Sprinkler Rough-in | 7/26/2004 | 7/27/2004 | 7/27/2004 12:00:00 AM | A | PASS |
|
|
Underground supply line is ok to cover 7/27/2004 2:39:04 PM
|
FIR04-00407
| INSP-Conference | 7/27/2004 | 7/27/2004 | 7/27/2004 12:00:00 AM | A | DONE |
|
|
There are card readers and door magnets being installed. I contacted Nick with Synergy and Jason with AEI about IFC and IBC requirements for access controlled egress doors. These items are not shown on the approved fire alarm plans. Plans will require possible resubmittals.
|
BLD04-00845
| FIRE-Final Inspection | 7/26/2004 | 7/27/2004 | 7/27/2004 12:00:00 AM | P | FAIL |
|
|
Fire alarm plans still have not been submitted to the city for approval 7/27/2004 3:57:55 PM
|
BLD03-01840
| FIRE-Final Inspection | 7/27/2004 | 7/27/2004 | 7/27/2004 12:00:00 AM | P | FAIL |
|
|
Provide "Door to remain unlocked while building is occupied" sticker at main entry/exits. Remove the dead bolt locks on all doors except the main entry/exit doors. Provide building address and suite numbers. Relocate fire hydrant so large outlet is accessible from the driveway. Paint curbing for fire dept. access per review note #11 and sheet A1.0. Install fire extinguishers per review note #13. Provide duct smoke detectors on units 2 and 3 per review note #27. 7/27/2004 1:54:48 PM
|
FIR03-00647
| INSP-Alarm Testing | 7/27/2004 | 7/27/2004 | 7/27/2004 12:00:00 AM | P | PART |
|
|
The fire alarm in the south wing, phase II per the building permit is tested and complete. 7/27/2004 3:57:03 PM
|
BLD03-01726
| FIRE-Final Inspection | 7/27/2004 | 7/27/2004 | 7/27/2004 12:00:00 AM | P | PASS |
|
|
Fire life safety for the shell only is OK 7/27/2004 10:47:02 AM
|