Inspections for the day of: Tuesday, July 27, 2004.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD03-02891 FIRE-Final Inspection7/26/20047/27/20047/27/2004 12:00:00 AMAFAIL
Inspection was for multiple rooms in the next phase of the project. See city approved plans, sheets A2.2, A2.3 and A2.5 for the specific rooms and deficiencies. There are card readers and door magnets being installed. I contacted Nick with Synergy and Jason with AEI about IFC and IBC requirements for access controlled egress doors. These items are not shown on the approved fire alarm plans. Plans will require possible resubmittals. 7/27/2004 10:27:32 AM
FIR04-00384 INSP-Sprinkler Rough-in7/26/20047/27/20047/27/2004 12:00:00 AMAPASS
Underground supply line is ok to cover 7/27/2004 2:39:04 PM
FIR04-00407 INSP-Conference7/27/20047/27/20047/27/2004 12:00:00 AMADONE
There are card readers and door magnets being installed. I contacted Nick with Synergy and Jason with AEI about IFC and IBC requirements for access controlled egress doors. These items are not shown on the approved fire alarm plans. Plans will require possible resubmittals.
BLD04-00845 FIRE-Final Inspection7/26/20047/27/20047/27/2004 12:00:00 AMPFAIL
Fire alarm plans still have not been submitted to the city for approval 7/27/2004 3:57:55 PM
BLD03-01840 FIRE-Final Inspection7/27/20047/27/20047/27/2004 12:00:00 AMPFAIL
Provide "Door to remain unlocked while building is occupied" sticker at main entry/exits. Remove the dead bolt locks on all doors except the main entry/exit doors. Provide building address and suite numbers. Relocate fire hydrant so large outlet is accessible from the driveway. Paint curbing for fire dept. access per review note #11 and sheet A1.0. Install fire extinguishers per review note #13. Provide duct smoke detectors on units 2 and 3 per review note #27. 7/27/2004 1:54:48 PM
FIR03-00647 INSP-Alarm Testing7/27/20047/27/20047/27/2004 12:00:00 AMPPART
The fire alarm in the south wing, phase II per the building permit is tested and complete. 7/27/2004 3:57:03 PM
BLD03-01726 FIRE-Final Inspection7/27/20047/27/20047/27/2004 12:00:00 AMPPASS
Fire life safety for the shell only is OK 7/27/2004 10:47:02 AM