Inspections for the day of: Wednesday, July 27, 2005.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-02634 Electrical Rough-In7/27/20057/27/20057/27/2005 4:27:33 PMPPASS
underground seth ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok to cover u/g to pole bases and to cover gec
ELE05-02227 Permanent Service7/27/20057/27/20057/27/2005 3:50:47 PMPPASS
CONTACT: LEWIS WARE; Phone #: ###-#### Internet Inspection Request from: Deb McCoy p/s u/g exst ok
ELE05-00842 Final7/27/20057/27/20057/27/2005 1:23:32 PMPFAIL
###-#### (also ###-#### Jamie) 408.4 panel schedule shall fully identify ckts, 314.17(C) nm cable shall be strapped within 8" of box (bath down), 406.5 cover plates shall seat against mounting surface (microwave and walls), 314.25 boxes shall have covers, BCC disposal shall be installed for final, called contr, left corr notice
ELE05-02663 Electrical Rough-In7/27/20057/27/20057/27/2005 1:05:09 PMPPASS
ron; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr made, ric ok
ELE05-02408 Final7/27/20057/27/20057/27/2005 1:00:38 PMPPASS
Scheduled by a contractor via Hello! on 7/27/2005 at 8:59:24 AM. Contact: ###-####. ok to final
ELE05-02663 Rough-In Permanent Service7/25/20057/27/20057/27/2005 10:18:33 AMACANC
clyde ###-#### see p/s and r/i
ELE04-03730 Final7/26/20057/27/20057/27/2005 9:51:05 AMAPASS
brian; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok to final
ELE05-01039 Final7/26/20057/27/20057/27/2005 9:20:58 AMAPASS
Scheduled by a contractor via Hello! on 7/26/2005 at 11:41:52 AM. Contact: ###-####. ok to final
ELE05-02688 Final7/26/20057/27/20057/27/2005 9:02:44 AMAPASS
brian ###-#### ok to final
ELE05-02670 Temporary Service7/25/20057/27/20057/27/2005 8:07:27 AMAPASS
allan ###-#### t/s u/g n ok
ELE04-02639 Electrical Rough-In7/26/20057/27/20057/27/2005 8:06:38 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Heather Packer soffits so end auditorium and north half of foyer ok to cover
ELE05-02663 Permanent Service7/27/20057/27/20057/27/2005 12:00:00 AMAPASS
clyde ###-#### p/s u/g n ok
ELE05-02663 Electrical Rough-In7/27/20057/27/20057/27/2005 12:00:00 AMAFAIL
clyde ###-#### called contr, left message, left corr notice, do not cover sign, BCC all make-up shall be done. Corner of kitchen had to be rebuilt after plumber went thru. Box hanging and 2x4 hanging on wire