Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00812 INSP-Supply line flush7/27/20057/27/20057/27/2005 3:11:46 PMAFAIL
Underground fire supply work appears to be installed in a satisfactory manner, however the resubmitted plans and notes with scope of work does not address phase 2 (connection to city supply) work. This work must be submitted and approved prior to field inspection and sign off.
FIR05-00401 INSP-Sprinkler Rough-in/Hydro7/27/20057/27/20057/27/2005 2:36:08 PMPPART
Overhead rough-in for antifreeze system at front canopy is acceptable to cover.
FIR05-00401 INSP-Sprinkler Rough-in/Hydro7/27/20057/27/20057/27/2005 12:00:00 AMPPART
Overhead hydrostatic test of antifreeze system at front canopy is satisfactory.
BLD04-02409 FIRE-Conference7/27/20057/27/20057/27/2005 12:00:00 AMPDONE
On site discussion with Nick the general contractor regarding fire department lane and street access requirements.