Inspections for the day of: Wednesday, July 27, 2005.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00358 INSP-Final Inspection7/27/20057/27/20057/27/2005 3:51:24 PMPCANC
Canceled by Orlen with SimplexGrinnell due to issues with the panel/new area.
FIR04-00633 INSP-Final Inspection7/27/20057/27/20057/27/2005 3:37:48 PMPPASS
See FIR05-00034 for the associated work.
FIR04-00737 INSP-Sprinkler Rough-in/Hydro7/27/20057/27/20057/27/2005 2:43:52 PMPCANC
Wrong permit called in. See FIR05-00124
FIR05-00124 INSP-Sprinkler Rough-in/Hydro7/27/20057/27/20057/27/2005 2:42:47 PMPPASS
Dry system hydro tested passed
FIR05-00124 INSP-Sprinkler Rough-in/Hydro7/27/20057/27/20057/27/2005 2:37:49 PMPFAIL
Inspection was for the cpvc piping in the existing areas. Wrong pendants installed. Will need to verify esch. for pendants. Need to provide eq. bracing for the cpvc mains
FIR04-00604 INSP-Final Inspection7/27/20057/27/20057/27/2005 2:03:20 PMPPASS
Permit finaled
BLD02-01235 FIRE-Alarm Testing7/26/20057/27/20057/27/2005 1:08:55 PMPPASS
Fire life safety finaled
BLD04-02272 FIRE-Final Inspection7/26/20057/27/20057/27/2005 12:11:19 PMAFAIL
Mount fire extinguishers as discussed. Change door hardware at restroom corridor to allow passage from corridor and along route as directed by exit signs. Test duct smoke detectors.
BLD04-02231 FIRE-Final Inspection7/26/20057/27/20057/27/2005 12:09:53 PMAPASS
Fire life safety finaled
FIR03-00510 INSP-Final Inspection7/25/20057/27/20057/27/2005 10:20:48 AMAFAIL
mike; Phone #: ###-#### Need to relocate the manual pull station to atleast 10' and no more than 20' from the cooking hood. Provide documents at final and retest pull station.
FIR04-00218 INSP-Final Inspection7/27/20057/27/20057/27/2005 9:11:23 AMPPASS
Permit finaled
FIR04-00505 INSP-Final Inspection7/27/20057/27/20057/27/2005 9:11:11 AMPPASS
Permit finaled
FIR04-00553 INSP-Final Inspection7/27/20057/27/20057/27/2005 9:10:57 AMPPASS
Permit finaled