FIR05-00358
| INSP-Final Inspection | 7/27/2005 | 7/27/2005 | 7/27/2005 3:51:24 PM | P | CANC |
|
|
Canceled by Orlen with SimplexGrinnell due to issues with the panel/new area.
|
FIR04-00633
| INSP-Final Inspection | 7/27/2005 | 7/27/2005 | 7/27/2005 3:37:48 PM | P | PASS |
|
|
See FIR05-00034 for the associated work.
|
FIR04-00737
| INSP-Sprinkler Rough-in/Hydro | 7/27/2005 | 7/27/2005 | 7/27/2005 2:43:52 PM | P | CANC |
|
|
Wrong permit called in. See FIR05-00124
|
FIR05-00124
| INSP-Sprinkler Rough-in/Hydro | 7/27/2005 | 7/27/2005 | 7/27/2005 2:42:47 PM | P | PASS |
|
|
Dry system hydro tested passed
|
FIR05-00124
| INSP-Sprinkler Rough-in/Hydro | 7/27/2005 | 7/27/2005 | 7/27/2005 2:37:49 PM | P | FAIL |
|
|
Inspection was for the cpvc piping in the existing areas. Wrong pendants installed. Will need to verify esch. for pendants. Need to provide eq. bracing for the cpvc mains
|
FIR04-00604
| INSP-Final Inspection | 7/27/2005 | 7/27/2005 | 7/27/2005 2:03:20 PM | P | PASS |
|
|
Permit finaled
|
BLD02-01235
| FIRE-Alarm Testing | 7/26/2005 | 7/27/2005 | 7/27/2005 1:08:55 PM | P | PASS |
|
|
Fire life safety finaled
|
BLD04-02272
| FIRE-Final Inspection | 7/26/2005 | 7/27/2005 | 7/27/2005 12:11:19 PM | A | FAIL |
|
|
Mount fire extinguishers as discussed. Change door hardware at restroom corridor to allow passage from corridor and along route as directed by exit signs. Test duct smoke detectors.
|
BLD04-02231
| FIRE-Final Inspection | 7/26/2005 | 7/27/2005 | 7/27/2005 12:09:53 PM | A | PASS |
|
|
Fire life safety finaled
|
FIR03-00510
| INSP-Final Inspection | 7/25/2005 | 7/27/2005 | 7/27/2005 10:20:48 AM | A | FAIL |
|
|
mike; Phone #: ###-#### Need to relocate the manual pull station to atleast 10' and no more than 20' from the cooking hood. Provide documents at final and retest pull station.
|
FIR04-00218
| INSP-Final Inspection | 7/27/2005 | 7/27/2005 | 7/27/2005 9:11:23 AM | P | PASS |
|
|
Permit finaled
|
FIR04-00505
| INSP-Final Inspection | 7/27/2005 | 7/27/2005 | 7/27/2005 9:11:11 AM | P | PASS |
|
|
Permit finaled
|
FIR04-00553
| INSP-Final Inspection | 7/27/2005 | 7/27/2005 | 7/27/2005 9:10:57 AM | P | PASS |
|
|
Permit finaled
|