Inspections for the day of: Thursday, July 27, 2006.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MIS06-00170 FIR-Final7/27/20067/27/20067/27/2006 4:09:50 PMPPASS
Life safety finaled
FIR06-00494 INSP-Final Inspection7/27/20067/27/20067/27/2006 4:09:20 PMPFAIL
No test performed since the gas was not turned on yet.
FIR06-00403 INSP-Sprinkler Rough-in7/26/20067/27/20067/27/2006 4:08:30 PMAFAIL
See approved plans for locations of needed corrections. They include sidewall heads mounted too low, head overspaced in bedroom, hanger ring unattached and missing piping.
BLD06-01243 FIRE-Final Inspection7/27/20067/27/20067/27/2006 12:29:44 PMPPASS
Life safety finaled
FIR06-00425 INSP-Final Inspection7/27/20067/27/20067/27/2006 12:29:27 PMPPASS
permit finaled. The overhead piping as shown on the plans does not match what was installed but after talking to Bill it will be approved.
FIR06-00414 INSP-Final Inspection7/27/20067/27/20067/27/2006 12:28:28 PMPPASS
permit finaled
FIR06-00414 INSP-Final Inspection7/27/20067/27/20067/27/2006 12:27:53 PMPPASS
permit finaled
BLD06-01453 FIRE-Final Inspection7/26/20067/27/20067/27/2006 12:26:15 PMAFAIL
The shell permit needs finaled and no approved drawings/notes were available. Also no fire extinguishers had been provided or door hardware installed. I did however see the address had been installed and the exit sign/emergency light worked.
FIR06-00414 INSP-Alarm Testing7/24/20067/27/20067/27/2006 12:00:05 PMAPASS
permit finaled
BLD05-03072 FIRE-Final Inspection7/26/20067/27/20067/27/2006 9:15:24 AMAPART
A temporary occupancy was given until the south tenant is complete
BLD05-03243 FIRE-Final Inspection7/26/20067/27/20067/27/2006 9:15:06 AMAPASS
A temporary occupancy was given until the south tenant is complete
BLD05-01262 FIRE-Final Inspection7/26/20067/27/20067/27/2006 9:14:52 AMAPART
A temporary occupancy was given until the south tenant is complete
FIR06-00104 INSP-Final Inspection7/26/20067/27/20067/27/2006 9:14:33 AMAPART
A temporary occupancy was given until the south tenant is complete