Inspections for the day of: Friday, July 27, 2007.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00460 INSP-Final Inspection7/26/20077/27/20077/30/2007 2:38:39 PMAFAIL
See correction notice left on site for defficient items, not all aspects tested at this time.
FIR07-00392 INSP-Final Inspection7/27/20077/27/20077/27/2007 5:09:25 PMPFAIL
Mag locks at two doors failed to drop out upon FA activation.
BLD07-00842 FIRE-Final Inspection7/26/20077/27/20077/27/2007 5:07:57 PMAFAIL
Need to add one and relocate exit signs as indicated, occupancy sensors at two doors do not function, need to final project related fire alarm permit prior to life safety final.
FIR06-00540 INSP-Sprinkler Rough-in/Hydro7/26/20077/27/20077/27/2007 5:05:47 PMAPART
Inspection for the 1st floor SW quad OH fire sprinkler install is conditionally approved for cover except as noted on plans and pending satisfactory resubmittals matching the initialed field plan set.
FIR07-00521 INSP-Sprinkler Rough-in/Hydro7/26/20077/27/20077/27/2007 5:02:30 PMAPASS
OH install passed final inspection.
FIR06-00583 INSP-Final Inspection7/27/20077/27/20077/27/2007 1:47:05 PMPPASS
Fire sprinkler permit passed final inspection, approved field modifications at two rooms, permit finaled.
FIR07-00359 INSP-Final Inspection7/25/20077/27/20077/27/2007 1:46:19 PMACANC
Matt - Thank you!! Phone #: ###-#### Internet Inspection Request from: Matt Casey Inspection cancelled from web by: Matt Casey
FIR07-00563 INSP-Final Inspection7/26/20077/27/20077/27/2007 1:40:34 PMAPASS
TI fire alarm work modifications passed field inspection, permit finaled.
FIR07-00275 INSP-Final Inspection7/26/20077/27/20077/27/2007 1:39:27 PMANH
No access provided.
BLD07-01257 FIRE-Final Inspection7/26/20077/27/20077/27/2007 1:38:01 PMAFAIL
Repair two exit signs, provide emergency lighting for the path of egress including the exit discharge per IFC 2003-see fire code review notes, doors at two locations are not installed-need to verify approved hardware.
FIR07-00540 INSP-Final Inspection7/26/20077/27/20077/27/2007 1:35:16 PMAPASS
C/N items are completed, fire alarm permit finaled.
FIR07-00040 FIR-Aging Inspection7/27/20077/27/20077/27/2007 9:41:13 AM DEFR
wip