Inspections for the day of: Friday, July 27, 2007.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00011 INSP-Alarm Testing7/27/20077/27/20077/27/2007 3:06:09 PMPDONE
See the city approved plans for Mike Timmermans notes and devices tested.
FIR05-00536 INSP-Sprinkler Rough-in7/26/20077/27/20077/27/2007 2:48:19 PMAPASS
See the third floor city approved drawings for the piping that is ok to cover.
FIR07-00534 INSP-Sprinkler Rough-in/Hydro7/26/20077/27/20077/27/2007 2:46:26 PMPPASS
The sprinkler piping is ok to cover. There are some minor corrections required which can be verified at the final. As-built drawings will be required prior to a final that reflect the changes in the pipe routing and the additional heads.
FIR07-00427 INSP-Final Inspection7/26/20077/27/20077/27/2007 1:39:47 PMAFAIL
See the city approved plans for corrections required. As-built plans will be needed showing the added heads.
FIR07-00419 INSP-Final Inspection7/26/20077/27/20077/27/2007 1:19:37 PMAFAIL
Relocate the smoke detectors 3' away from the ceiling fan blade tips, provide the required audio level at the pillows and sync the audio devices.
BLD07-01930 FIRE-Final Inspection7/26/20077/27/20077/27/2007 11:44:51 AMAPASS
Life safety passed. Owner was in the process of installing the suite address
BLD06-03378 FIRE-Final Inspection7/26/20077/27/20077/27/2007 10:48:45 AMAFAIL
The south and the east exit discharge lights did not work. The north and south exit doors need approved hardware and the deadbolts removed. Per the plans there are three hvac units that require duct smoke detectors. I did not see remote annunciators as required. These duct detectors, if even installed, will need to be tested.
FIR06-00570 INSP-Final Inspection7/26/20077/27/20077/27/2007 10:30:00 AMAPASS
Permit finaled
FIR07-00493 INSP-Final Inspection7/26/20077/27/20077/27/2007 8:23:08 AMAFAIL
Two sprinkler heads have been painted under the west stairs.