Inspections for the day of: Monday, July 27, 2009.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00420 INSP-Sprinkler Rough-in7/27/20097/27/20097/27/2009 4:33:01 PMPPART
Overhead modifications at 6 new focus rooms are approved for cover per plan annotations initialed with todays date, noted the four new rooms to the east are not yet built.
FIR08-00444 INSP-Final Inspection7/27/20097/27/20097/27/2009 4:08:27 PMPPASS
Fire sprinkler permit finaled.
FIR08-00444 INSP-Sprinkler Rough-in/Hydro7/27/20097/27/20097/27/2009 4:08:03 PMPPART
Correction item verified for completion, inspection passed.
FIR08-00571 INSP-Sprinkler Rough-in/Hydro7/27/20097/27/20097/27/2009 4:04:35 PMPPART
Overhead install at unit 1501 okayed for cover.
FIR09-00282 INSP-Sprinkler Rough-in7/27/20097/27/20097/27/2009 4:02:51 PMPPART
Approved overhead cover for unit 101 and 201east side 516.
FIR09-00033 INSP-Sprinkler Rough-in/Hydro7/21/20097/27/20097/27/2009 4:00:45 PMAPART
Overhead hydrostatic testing completed okay for systems 13, 15, riser room #1, 19, 20 and system 16 not including racks.
BLD09-00537 FIRE-Final Inspection7/27/20097/27/20097/27/2009 1:26:43 PMPPASS
Fire life safety inspection for remaining areas including A and C completed satisfactory.
FIR09-00316 INSP-Final Inspection7/27/20097/27/20097/27/2009 1:25:14 PMPPASS
Notification in areas A and C passed field testing, mag locks at one location tied in and tested while on site, fire alarm permit finaled.
FIR09-00358 INSP-Final Inspection7/27/20097/27/20097/27/2009 1:23:39 PMAPASS
Fire sprinkler work in the remainder of remodel areas A and C passed final walkthrough, permit okayed for final.
BLD09-01227 FIRE-Final Inspection7/24/20097/27/20097/27/2009 1:21:31 PMAFAIL
Provide approved door hardware at three locations including the main entries to suites 6, 8 and 9, the fire extinguisher in suite 9 is overdue annual certification.
BLD08-02530 BLD-Aging Inspection7/27/20097/27/20097/27/2009 9:05:56 AM FAIL
Missing plans to complete inspection.