Inspections for the day of: Tuesday, July 27, 2010.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE10-00849 ELE-Aging Inspection7/27/20107/27/20107/28/2010 6:32:05 AM DONE
suc
ELE10-01345 Final7/26/20107/27/20107/27/2010 2:49:54 PMPCANC
final on wiring, any questions call Rob @ ###-#### Phone #: ###-#### >> Inspection requested via web by Andy Rose customer called asked to cancel, will recall for tomorrow
ELE10-01653 Electrical Rough-In7/26/20107/27/20107/27/2010 2:41:11 PMPPART
Kevin-East side from the corridor over of suite 100 inspected only please Phone #: ###-#### east side corridor walls only ok to cover
ELE10-01625 Electrical Rough-In7/26/20107/27/20107/27/2010 1:47:04 PMPPASS
You will have to call Steve to get to the 2oth Floor. ###-#### Phone #: ###-#### >> Inspection requested via web by Kevin Perez walls only ok
ELE10-01508 Electrical Rough-In7/27/20107/27/20107/27/2010 1:12:44 PMPPASS
fred - please call 1/2 hr prior so he can meet you there Phone #: ###-#### ri ok
ELE10-01467 Final7/26/20107/27/20107/27/2010 10:42:29 AMAPASS
ready for final Phone #: ###-#### >> Inspection requested via web by gary batten called, ok final
ELE10-01622 Rough-In Permanent Service7/26/20107/27/20107/27/2010 10:31:02 AMAPASS
THANK YOU, BOB Phone #: ###-#### >> Inspection requested via web by Bob Glenn ri ok, p/s u/g n ok
ELE10-01652 Rough-In Permanent Service7/26/20107/27/20107/27/2010 9:59:26 AMAPASS
If you have any question, please call Clay. Phone #: ###-#### >> Inspection requested via web by Clay Morgan ri ok, p/s o/h n ok
ELE10-01587 Temporary Service7/27/20107/27/20107/27/2010 9:25:30 AMAPASS
t/s u/g n ok
ELE10-01655 Electrical Rough-In7/26/20107/27/20107/27/2010 9:22:11 AMAFAIL
Phone #: ###-#### >> Inspection requested via web by Clint Tate left correction notice to owner, NEC 314.17 conductors shall have abrasion protection, 314.4 metal boxes shall be grounded and bonded per NEC article 250, NOTE corrections shall be made within 5 working days or further action will be taken
ELE10-01336 Electrical Rough-In7/26/20107/27/20107/27/2010 8:48:27 AMAFAIL
3rd floor lobby ceiling cover Phone #: ###-#### >> Inspection requested via web by Tyler Bowen ceiling tiles partly up, needs tie wires, box closed, will call when ready
ELE10-01354 Conference7/23/20107/27/20107/27/2010 8:29:08 AMADONE
This conference has been scheduled for 8:00am. Nick is the contact his no. is ###-####. Thank you. Phone #: ###-#### >> Inspection requested via web by Shawna Gates talked about field evaluation for service and adding new disconnect
ELE10-01354 Electrical Rough-In7/27/20107/27/20107/27/2010 8:28:57 AMAPASS
This conference has been scheduled for 8:00am. Nick is the contact his no. is ###-####. Thank you. Phone #: ###-#### >> Inspection requested via web by Shawna Gates basement closet walls only ok to cover
ELE10-01108 Final7/27/20107/27/20107/27/2010 6:39:09 AMAPASS
ok to final
ELE08-02665 DOC - Permit Expired7/27/20107/27/20107/27/2010 6:32:26 AMAPASS
no activity