Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-00903 ELE-Aging Inspection7/27/20157/27/20157/30/2015 10:20:10 AM CANC
too busy
ELE13-00908 ELE-Aging Inspection7/27/20157/27/20157/30/2015 10:19:50 AM CANC
Too busy
ELE15-01324 Final7/27/20157/27/20157/27/2015 3:46:34 PMPPASS
Phone #: ###-#### Inspection requested via web by Cyndi Dale Final ok
ELE15-02316 Electrical Rough-In7/27/20157/27/20157/27/2015 3:20:47 PMPPASS
Contact is Darrin Allen ###-#### Phone #: ###-#### Inspection requested via web by Scott Campbell Dividing wall rough in ok cover
ELE15-02028 Final7/27/20157/27/20157/27/2015 2:30:49 PMPCANC
JIm Phone #: ###-#### Unable to final due to power not connected yet.
ELE15-02028 Permanent Service7/27/20157/27/20157/27/2015 2:30:29 PMPPASS
JIm Phone #: ###-#### p/s u/g n ok
ELE15-02229 Permanent Service7/27/20157/27/20157/27/2015 2:01:39 PMPFAIL
Becky// please call for access Phone #: ###-#### BCC 4-05-32- Code violation not to be retained. BCC 4-05-31(C)- Unfused conductors shall not enter structure. NEC 230.70- A means shall be provided to disconnect all conductors in a building from the service entrance conductors. NEC 250.53(a)(2)- Underground metal water pipe used as grounding electode shall have a supplemental rod installed. NEC 110.3(A)- Neutral branch circuit conductor shows evidence of arcing in panel. Must have electrical contractor make corrections.
ELE15-02210 Electrical Rough-In7/24/20157/27/20157/27/2015 1:07:58 PMPPASS
We are requesting a wall rough-in inspection for Monday 7/27/15 in the afternoon. Our onsite contact is Rich @ ###-####. Thank you Phone #: ###-#### Inspection requested via web by Clint Tate West wall by J-3 to J-5 and storage area wall rough in ok cover
ELE15-02169 Electrical Rough-In7/24/20157/27/20157/27/2015 12:12:08 PMAPASS
Please call the office if you have any questions. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan Attached to BLD12-00712. Underground rough in ok cover
ELE15-02300 Electrical Rough-In7/24/20157/27/20157/27/2015 9:47:10 AMAPASS
Kevin Phone #: ###-#### No solar. Low volt LED lights. bonds 4 corners, 2 at cover. Underground for pool rough in ok cover. 2 2" from patio down hill not part of this permit
ELE15-02308 Rough-In Permanent Service7/24/20157/27/20157/27/2015 9:04:27 AMAFAIL
Phone #: ###-#### Inspection requested via web by TOM BICANDI 250.24(A)- Grounded service shall have a grounding electrode installed. Unable to locate concrete encased.
300.4- Nail plates needed in room back of garage in corner and SER in kitchen area.
All WUI zone soffit lights are 2 gang 2 hour fire rated boxes OK
OK to foam seal