BLD14-03207
| FIRE-Conference | 7/27/2016 | 7/27/2016 | 7/27/2016 4:37:42 PM | A | DONE |
|
|
Fire conference complete. Discussed modifications to exit light placement/direction. Items that still need to be inspected: emergency egress lighting, fire alarm audio visual testing, in duct smoke detectors, mag lock release on fire doors, stairwell pressurization system, emergency power transfer and placement verificaion of fire extinguishers with current inspection tags from a licensed contractor.
|
FIR16-00321
| INSP-Final Inspection | 7/27/2016 | 7/27/2016 | 7/27/2016 4:09:53 PM | P | CANC |
|
|
Final clean agent suppression system inspection cancelled, contractor not ready for final inspection.
|
BLD15-03767
| FIRE-Final Inspection | 7/27/2016 | 7/27/2016 | 7/27/2016 4:04:49 PM | P | CANC |
|
|
Inspection request cancelled, FIR permits for fire alarm and fire sprinklers still in issued status, inspections for these permits needs to be completed and passed before life fire safety inspection can be performed.
|
FIR15-00806
| INSP-Sprinkler Rough-in | 7/27/2016 | 7/27/2016 | 7/27/2016 12:14:46 PM | P | PASS |
|
|
Tenting insulation inspection complete for overhead fire sprinkler piping located in attic spaces, overhead fire sprinkler piping approved for cover.
|
FIR15-00727
| INSP-Final Inspection | 7/26/2016 | 7/27/2016 | 7/27/2016 11:47:24 AM | A | CANC |
|
|
Inspection request cancelled per conversation with point of contact, Mike phone number ###-####.
|
FIR15-00903
| INSP-Final Inspection | 7/26/2016 | 7/27/2016 | 7/27/2016 11:36:39 AM | A | PASS |
|
|
Final fire sprinkler inspection for level 5 passed/complete
|
FIR16-00204
| INSP-Final Inspection | 7/26/2016 | 7/27/2016 | 7/27/2016 11:33:38 AM | A | PASS |
|
|
Final fire sprinkler inspection for level 7 preaction system passed/complete.
|
FIR16-00204
| INSP-Conference | 7/26/2016 | 7/27/2016 | 7/27/2016 11:30:39 AM | A | PASS |
|
|
24 hour batter test passed/complete.
|
BLD15-03584
| FIRE-Final Inspection | 7/27/2016 | 7/27/2016 | 7/27/2016 9:30:00 AM | A | PASS |
|
|
Fire sprinkler inspection complete, fire alarm inspection complete, core and shell is considered unoccupied space until tenant improvements are made so no fire extinguishers are installed. Final life fire safety inspection passed/complete.
|
FIR16-00137
| INSP-Final Inspection | 7/26/2016 | 7/27/2016 | 7/27/2016 9:16:57 AM | A | PASS |
|
|
Final fire alarm inspection passed/complete
|