Inspections for the day of: Wednesday, July 27, 2016.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD14-03207 FIRE-Conference7/27/20167/27/20167/27/2016 4:37:42 PMADONE
Fire conference complete. Discussed modifications to exit light placement/direction. Items that still need to be inspected: emergency egress lighting, fire alarm audio visual testing, in duct smoke detectors, mag lock release on fire doors, stairwell pressurization system, emergency power transfer and placement verificaion of fire extinguishers with current inspection tags from a licensed contractor.
FIR16-00321 INSP-Final Inspection7/27/20167/27/20167/27/2016 4:09:53 PMPCANC
Final clean agent suppression system inspection cancelled, contractor not ready for final inspection.
BLD15-03767 FIRE-Final Inspection7/27/20167/27/20167/27/2016 4:04:49 PMPCANC
Inspection request cancelled, FIR permits for fire alarm and fire sprinklers still in issued status, inspections for these permits needs to be completed and passed before life fire safety inspection can be performed.
FIR15-00806 INSP-Sprinkler Rough-in7/27/20167/27/20167/27/2016 12:14:46 PMPPASS
Tenting insulation inspection complete for overhead fire sprinkler piping located in attic spaces, overhead fire sprinkler piping approved for cover.
FIR15-00727 INSP-Final Inspection7/26/20167/27/20167/27/2016 11:47:24 AMACANC
Inspection request cancelled per conversation with point of contact, Mike phone number ###-####.
FIR15-00903 INSP-Final Inspection7/26/20167/27/20167/27/2016 11:36:39 AMAPASS
Final fire sprinkler inspection for level 5 passed/complete
FIR16-00204 INSP-Final Inspection7/26/20167/27/20167/27/2016 11:33:38 AMAPASS
Final fire sprinkler inspection for level 7 preaction system passed/complete.
FIR16-00204 INSP-Conference7/26/20167/27/20167/27/2016 11:30:39 AMAPASS
24 hour batter test passed/complete.
BLD15-03584 FIRE-Final Inspection7/27/20167/27/20167/27/2016 9:30:00 AMAPASS
Fire sprinkler inspection complete, fire alarm inspection complete, core and shell is considered unoccupied space until tenant improvements are made so no fire extinguishers are installed. Final life fire safety inspection passed/complete.
FIR16-00137 INSP-Final Inspection7/26/20167/27/20167/27/2016 9:16:57 AMAPASS
Final fire alarm inspection passed/complete