Inspections for the day of: Thursday, July 27, 2017.
Number of inspections: 1
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBill VanDegrift
TitlePLM-INSPECTOR
Phone #794-9372
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC03-02091 Final7/27/20177/27/20177/27/2017 4:53:33 PMPFAIL
Elena-w/h Phone #: ###-####

went by to put final stickers on the furnace and waterheaters but one water heater was in a bedroom that one will need a solid sealed door with all combustion air from the outside and the water heater flex removed from the relief line it also needs 6 inches of clearance at the single wall flue at the shelf above. the water heater in the hallway needs the water heater flex removed from the relief line. the furnace is ok.