Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-01470 Final7/26/20187/27/20187/27/2018 3:28:15 PMPPART
Please call Corey when onsite. If at all possible we would like this as late in the afternoon as possible. Phone #: ###-#### Inspection requested via web by Kevin Perez
Perimeter walls need access to all receptacles for final, all safe.
Level 2 TCO ok
ELE18-01323 Final7/26/20187/27/20187/27/2018 2:38:11 PMAFAIL
Please call 30 to 60 minutes before inspection so we can provide an escort for inspection. Phone #: ###-#### Inspection requested via web by Scott Campbell
110.7- Wires pinched by ballast cover in reception area.

300.11- Speakers shall be supported independant of grid as per Dave Hanna.
314.25- All boxes containing a splice shall have a cover. Reception area.
400.12- Flexible cords shall not penetrate or run above ceiling grid. Projector.
As noted on print 2012 IECC shall comply. Dual switching as noted on print shall reduce loads by at least 50%. Intern area 3-1, offices 2-0, conference room lighting most not working, Reception area OK.
ELE17-03784 Final7/27/20187/27/20187/27/2018 2:02:13 PMPPASS
George Morris is contact at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce Final ok
ELE18-01789 Final7/27/20187/27/20187/27/2018 12:52:09 PMPCANC
Phone #: ###-#### Inspection requested via web by Don Conley
Contact sent message... lights did not come in, should reschedule for Monday
ELE18-02792 Electrical Rough-In7/26/20187/27/20187/27/2018 11:58:37 AMAPASS
Phone #: ###-#### Inspection requested via web by Michael Hobson rough-in ok cover family room addition
ELE18-02850 Electrical Rough-In7/26/20187/27/20187/27/2018 11:51:37 AMAPASS
Phone #: ###-#### Inspection requested via web by Steve Craig
Wires hanging from ceiling to terminate into luminaires. Wall and hardlids rough in ok cover
ELE18-02753 Electrical Rough-In7/26/20187/27/20187/27/2018 9:36:06 AMAPASS
garage code 1001e Phone #: ###-#### Inspection requested via web by Alan Lusk Rough in ok cover
ELE18-02753 Permanent Service7/27/20187/27/20187/27/2018 9:35:58 AMPPASS
garage code 1001e Phone #: ###-#### Inspection requested via web by Alan Lusk p/s u/g n ok