FIR04-00176
| INSP-Final Inspection | 7/27/2004 | 7/28/2004 | 7/28/2004 12:00:00 AM | A | PART |
|
|
mark; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Gift shop area only okay; will test EOL's at end of project; AD detectors by storage room deleted as they were not required 7/28/2004 8:39:10 AM
|
FIR04-00230
| INSP-Final Inspection | 7/27/2004 | 7/28/2004 | 7/28/2004 12:00:00 AM | A | PASS |
|
|
nick; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
BLD03-02673
| FIRE-Conference | 7/27/2004 | 7/28/2004 | 7/28/2004 12:00:00 AM | A | FAIL |
|
|
rory; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Address; handrails; extinguishers; doors not installed (see hardware schedule for all doors) 7/28/2004 9:13:34 AM
|
BLD03-02791
| FIRE-Final Inspection | 7/28/2004 | 7/28/2004 | 7/28/2004 12:00:00 AM | A | PART |
|
|
Gift shop area only okay to occupy; fire alarm and sprinklers okay in this area 7/28/2004 8:44:59 AM
|
BLD03-02023
| FIRE-Final Inspection | 7/28/2004 | 7/28/2004 | 7/28/2004 12:00:00 AM | A | PASS |
|
|
fire sprinklers finalled; smoke detectors tested okay 7/28/2004 12:13:42 PM
|
FIR03-00343
| INSP-Final Inspection | 7/28/2004 | 7/28/2004 | 7/28/2004 12:00:00 AM | P | FAIL |
|
|
Inspection was stopped as the alarms/flows/tampers weren't thoroughly pre-tested (low air didn't function/OS & Y tampers required adjustments; pump controller not reporting power loss as it was wired backwards) 7/28/2004 4:03:17 PM
|
FIR03-00613
| INSP-Final Inspection | 7/27/2004 | 7/28/2004 | 7/28/2004 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 7/27/2004 at 3:13:05 PM. Contact: ###-####. Inspection stopped due to sprinkler alarm problems - system not pre-tested; need updated plans to reflect added tampers/flows; descriptors needed for dry tampers/flows - all room numbers in basement are construction room numbers; need to verify inter-connection to PA2 7/28/2004 4:01:06 PM
|